Welcome Customer !

Membership

Help

Xi'an Shengli Instrument Co., Ltd
Custom manufacturer

Main Products:

instrumentb2b>Products

Xi'an Shengli Instrument Co., Ltd

  • E-mail

  • Phone

  • Address

    25th Floor, Building G, Wangzuo Modern City, No. 35 Tangyan Road, High tech Zone, Xi'an City, Shaanxi Province

Contact Now

VICTOR 4120 Transformer Ratio Tester

NegotiableUpdate on 05/14
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

The VICTOR 4120 transformer ratio tester uses microprocessor technology for measurement calculation and automated control, which can quickly and easily measure the actual ratio and group of transformers. Mainly used for measuring transformer ratio and group in the power industry, and also for measuring various parameters of transformers by transformer manufacturers and distributors.

Product Details

The VICTOR 4120 transformer ratio tester uses microprocessor technology for measurement calculation and automated control, which can quickly and easily measure the actual ratio and group of transformers. Mainly used for measuring transformer ratio and group in the power industry, and also for measuring various parameters of transformers by transformer manufacturers and distributors.
The VICTOR 4120 transformer ratio tester consists of a host, monitoring software, testing lines, communication lines, etc. The host has a charging function that does not require on-site power searching, a full-color large screen LCD display, and the language can be selected from Chinese or English, which is clear at a glance. The touch screen operation is convenient and easy to use, and the port has overload prevention function. It has a large capacity to store 500 sets of data. The upper computer software has functions such as reading, consulting, and saving historical data.
Technical Indicators:

Measurement ratio range resolution precision
0.9 × 8806; TTR<10 0.0001 ±0.2%±2dgt
10 pill8806; TTR<100 0.001 ±0.2%±2dgt
100≦TTR<1000 0.01 ±0.2%±2dgt
1000≦TTR<2000 0.1 ±0.2%±2dgt
2000≦TTR<10000 0.1 ±0.5%±2dgt
10000 at 880707R;TTR 1 --


Technical specifications:

Function Mainly used for ratio and group testing of three-phase transformers, as well as ratio and polarity testing of single-phase transformers, PT, and CT. This product can perform blind testing on three-phase transformers, as well as ratio and group testing on Z-type transformers.
Sample type Single phase transformer, three-phase transformer, Z-type transformer PT、CT
Variable ratio range 0.9~10000
overload protection have
Power supply DC9.6V 3800mAh high-capacity lithium battery
charging function have
display mode 5-inch touch screen (854dots × 480dots) full-color LCD display
interaction method Touch screen/buttons
LCD size Length and width: 108mm × 65mm
Instrument size Length, width, and height: 229mm × 166mm × 74mm
mobile app Yes, Bluetooth connection
Computer upper computer Yes, USB cable connection
data storage 500 sets
data lookup Data retrieval function
battery voltage Real time display of battery level, indicating the need for timely charging when the battery voltage is low
Auto Shutdown Can be set to automatically shut down within 1-30 minutes
Power consumption Standby: Approximately 2W (100% brightness)
Measurement: 12W Max
Quality Instrument: 1.5kg (including battery)
Test line: 1.7kg
Working temperature and humidity -10℃~40℃; Below 70% RH
Storage temperature and humidity -20℃~60℃; Below 70% RH
insulation resistance Above 10M Ω (500V between circuit and casing)
Voltage resistance AC 3700V/rms (between circuit and casing)
electromagnetic properties IEC61010-4-3, Wireless frequency electromagnetic field ≤ 1V/m
Suitable for safety regulations IEC61010-1, CAT III 600V, Pollution Level 2