1Reclaimed water reuse systemTypical processing flow
Raw water (sewage/wastewater/RO concentrate)
↓
Flocculation sedimentation tank → multi-media filtration → activated carbon filtration → ultrafiltration → RO system → disinfection → finished water (tap water grade)
2、 Core process of the system
1. Preprocessing stage
Flocculation and sedimentation:
Add polyaluminum chloride (PAC) and polyacrylamide (PAM) to form flocs through coagulation reaction, removing suspended solids (SS), colloids, and some organic matter.
SS ≤ 50mg/L after precipitation
COD≤200mg/L。
Multi media filter:
Quartz sand+smokeless coal+magnetite filter material, further removing fine particles and reducing turbidity to ≤ 5NTU.
Activated carbon filter:
Absorb organic matter, residual chlorine, color and odor, improve water quality and taste.
2. Deep processing stage
Ultrafiltration (UF):
0.01-0.1 μ m hollow fiber membrane, capable of intercepting bacteria, viruses, and large organic molecules, with water turbidity ≤ 0.5NTU and SDI ≤ 3.
Reverse osmosis (RO):
Under high pressure drive, the RO membrane (desalination rate ≥ 97%) removes inorganic salts, heavy metals, and microorganisms, and the conductivity of the produced water is ≤ 10 μ S/cm, meeting the standard for purified water.
3. Post processing stage
UV+ozone combined disinfection:
Ultraviolet (UV) radiation destroys microbial DNA, while ozone (O3) oxidizes residual organic matter and sterilizes, ensuring a total bacterial count of ≤ 100 CFU/mL.
3、 Comparison of water quality indicators
indicator |
Inlet water quality (example) |
Outlet water quality (standard for tap water) |
Turbidity (NTU) |
≤50 |
≤1.0 |
COD(mg/L) |
≤500 |
≤30 |
Ammonia nitrogen (mg/L) |
≤50 |
≤0.5 |
Total hardness (calculated as CaCO3) |
≤800 |
≤450 |
Conductivity (μ S/cm) |
≤3000 |
≤ 1000 (municipal tap water) |
Total colony count (CFU/mL) |
≤10⁶ |
≤100 |
4Reclaimed water reuse systemadvantage
1. Stable and up to standard water quality: Through RO membrane and multi-stage disinfection, ensure that indicators such as heavy metals and microorganisms are superior to conventional tap water.
2. High recovery rate: RO concentrated water can be refluxed to the pretreatment system, with a total water recovery rate of ≥ 85%.
3. Modular design: The processing capacity can be flexibly configured from 10m ³/d to 1000m ³/d to adapt to different scenarios.
4. Intelligent operation and maintenance:
Real time feedback on online water quality monitoring (pH, conductivity, residual chlorine, etc.).
Automatic chemical cleaning (CIP) of membrane components to extend their service life.
5、 Applicable scenarios
Industrial water: pure water preparation for electronic plants, boiler feedwater.
Municipal water supply: Supplement drinking water in water scarce areas and ensure emergency water supply.
Commercial project: Hotel direct drinking water, scenic area circulating water system.
RO concentrated water reuse: The concentrated water in the reverse osmosis system is reprocessed to reduce wastewater discharge.
6、 Policies and Cases
Policy support: The national "14th Five Year Plan" for the development of urban sewage treatment and resource utilization encourages "quality and grading reuse", and some provinces and cities provide a 30% equipment subsidy for high-quality reuse projects.