- Phone
-
Address
No. 23 Haiwo Road, Guangling District, Yangzhou City
Jiangsu Jiuyi Electric Power Equipment Co., Ltd
No. 23 Haiwo Road, Guangling District, Yangzhou City
Introduction
It is an important testing tool to ensure the safe and reliable operation of the power system. With the continuous expansion of modern power systems and the increasing demand for reliability and efficiency in power system operation and management, the testing work of relay protection personnel has become more frequent and complex.In today's rapidly developing computer technology, microelectronics technology, and power electronics technology, the continuous introduction of new high-performance relay protection testers using the latest technological achievements is an inevitable trend of technological progress and a responsibility entrusted to us by the times.
Product Features
1. Support multiple relay protection devices: can test multiple relay protection devices, including digital relay protection devices, microcomputer relay protection devices, automatic setting devices, auxiliary protection devices, etc.
2. High precision testing: With high-precision testing functions, it can test the braking time, action time, release time, three-phase unbalanced current ratio, phase sequence, failure criteria and other parameters of various relay protection relays.
3. Strong programmability: With flexible programming capabilities, users can write custom test scripts as needed to achieve various complex testing tasks.
4. Wide detection range: It can detect relay protection devices of various levels and types in the power system, including protection transformers, generators, transmission lines, and distribution lines.
5. Easy to operate: Using a graphical user interface, the operation is simple and easy to learn, with a friendly interface and user-friendly interaction design.
6. Stable and reliable: Using high-performance analog circuits and digital processors, it has high stability and reliability.
rated parameters
parameter
type number |
|
Number of current channels |
Standard 6-phase |
Number of voltage channels |
Standard 6-phase |
AC current output range |
30A/phase or 180A (six in one) |
DC current output range |
10ADC/phase |
AC voltage output range |
120VAC/phase |
DC voltage output range |
160VDC/phase |
rated parameters
AC current output
When outputting 6-phase current, each phase outputs (effective value) 0-30A with an output accuracy of 0.2 level
When outputting 3-phase current, each phase outputs (effective value) 0-60A
6-phase parallel current output (effective value) 0-180A
Long term allowable operating value (effective value) of phase current 10A
Maximum output power of phase current 300VA
Maximum output power of 1000VA at maximum output of 6-phase parallel current
The maximum allowable working time for 6-phase parallel current output is 10 seconds
Frequency range (fundamental) 20-1000Hz
Harmonic order 1-20 times
DC current output
Current output 0~± 10A/output accuracy of 0.5 level per phase
Maximum output load voltage 20V
AC voltage output
Phase voltage output (effective value) 0-120V output accuracy 0.2 level
Line voltage output (effective value) 0-240V
Phase voltage/line voltage output power 80VA/100VA
Frequency range (fundamental) 20-1000Hz
Harmonic order 1-20 times
DC voltage output
Phase voltage output amplitude 0~± 160V output accuracy 0.5 level
Line voltage output amplitude 0~± 320V
Phase voltage/line voltage output power 70VA/140VA
discrete signal
8-way switch input
Empty contact 1-20mA, 24V
Potential contact connected to "0": 0~+6V; “1”:+11 V ~ +250 V
4 pairs of switch output DC: 220 V/0.2 A; AC:220 V/0.5 A
Time measurement range
0.1ms ~ 9999s , Measurement accuracy < 0.1mS