Technical Specifications
|
·Measurement range
|
Minimum measurement range 0~500Pa, maximum measurement range 0~4MPa
|
|
|
·Accuracy
|
The comprehensive error (including linearity, repeatability, and hysteresis) is better than 0.1%
|
|
|
|
<7KPa: 0.25% rated range 1:1~3:1 (0.25% standard range+0.03% TD)%
|
|
|
|
Set the range to 3:1 to 10:1
|
|
|
|
≥ 7kPa: 0.2% standard range 1:1~3:1 (0.2% standard range+0.03% TD)%
|
|
|
|
Set the range to 3:1 to 10:1
|
|
|
·Long term stability
|
Annually ≤ ± 0.15% Fs
|
|
|
·Working temperature
|
Allowable medium temperature (-40~100) ℃, allowable storage temperature (-40~85) ℃
|
|
|
|
Allowable ambient temperature (-20~60) ℃ (special requirement -40~85 ℃)
|
|
|
·Temperature influence
|
-Within the temperature range of 20 ℃ to+60 ℃, the influence error (zero point, range) is ≤ 0.8%
|
|
|
|
The influence error of the 7KPa range sensor is ≤ 1.2%
|
|
|
·Temperature coefficient
|
-10 ℃~+60 ℃ (0.05% URL+0.065% set range)/20K
|
|
|
|
-40 ℃~-10 ℃ 60 ℃~+85 ℃ (0.08% URL+0.1% set range)/20K
|
|
|
·Long term stability and qualitative analysis
|
Better than 0.1% FS per year and better than 0.25% for five years
|
|
|
·Sensors allow
Working static pressure
|
Unidirectional and bidirectional maximum allowable static pressure PN13MPa
|
|
|
·Static pressure influence
|
Under 100% condition, the impact is ≤ 0.25%
|
|
|
·Damping
|
0-40 seconds continuously adjustable
|
|
|
·Allow environmental humidity
|
100%HR
|
|
|
·Signal output
|
4-20mA linear output two-wire system with HART communication protocol
|
|
|
|
4-20mA square root output two-wire system with HART communication protocol
|
|
|
·Start time
|
3S without preheating required
|
|
|
·Vibration impact
|
2g 1000HZ ±0.05%
|
|
|
·Impact resistance
|
50g 11mesc
|
|
|
·Load characteristics
|
Corresponding to power supply voltage impedance of 50 Ω~1000 Ω (see figure)
|
|
|
·Power supply
|
12V~36V DC
|
|
|
·Sensor range ratio
|
20: 1. Continuously adjustable, zero point can be reversed and migrated 100%
|
|
|
·Installation location impact
|
Non horizontal installation generates a zero point error of less than 0.25KPa, which can be corrected by adjusting the zero point,
|
|
|
|
Does not affect measurement accuracy
|
|
|
·Electrical connection
|
The cable sealing shell is suitable for cables with an outer diameter of 6-8mm;
|
|
|
·Process Connection
|
1/4NPT internal thread; Connection of pressure conduit; M10 internal hole thread; Installation bracket connection
|
|
|
·Contact with medium
|
Sensor corrugated membrane: stainless steel 316L, Hastelloy C;
|
|
|
Partial materials
|
Sensor sealing ring: Fluorine rubber EPDM, PTFE carat (Kalrez);
|
|
|
|
Flange: Stainless steel 316, Hastelloy C
|
|
|
·Non contact with the medium
|
Shell: Die cast aluminum strip with epoxy resin coating; Fastener: Stainless steel
|
|
|
Partial materials
|
Nameplate: Stainless steel 304; Intermediate fluid in sensor: silicone oil
|
|
|
·On site terminal
|
Intelligent: 5-digit LCD digital display; Simulation: 3 1/2 digit LCD digital display
|
|
|
·Explosion proof level
|
Explosion proof Ex d Ⅱ C T6 Gb; Intrinsically safe Ex ia Ⅱ C T6 Ga
|