- Phone
-
Address
Room 1205-A18, No. 968, 128th Memorial Road, Baoshan District, Shanghai
Shanghai Suhuo Electric Co., Ltd
Room 1205-A18, No. 968, 128th Memorial Road, Baoshan District, Shanghai
The SF6 gas leakage intelligent monitoring and alarm system is an intelligent online monitoring system designed and developed in accordance with the SF6 Safety Regulations to provide personal health and safety protection for workers in distribution equipment rooms equipped with SF6 equipment.SF6 gas leakage alarm deviceThe main function is to detect the concentration and oxygen content of SF6 gas in the switch room. When the SF6 gas content in the environment exceeds the standard or there is oxygen deficiency, an alarm can be triggered in real time, and the ventilation fan can be automatically turned on for ventilation. It also has many rich functions such as temperature and humidity detection, working status voice prompt, remote alarm, and historical data query. He has a trace SF6 gas detection technology that can detect SF6 gas with a concentration of 10-5000ppm, which not only ensures personal safety but also ensures the normal operation of equipment; Imported highly stable oxygen sensors can provide more reliable protection for on-site workers.
This system can be widely used in SF6 switch rooms, SF6 switch rooms, combination electrical rooms (GIS rooms), SF6 main transformer rooms, etc. of various voltage levels.
Main Features
Automatically start the fan exhaust function when there is an over limit alarm leakage;
O2 content detection function in the environment, automatic alarm and exhaust in case of hypoxia;
Large screen LCD dynamic Chinese display with automatic screen protection function. User friendly interface, fast refresh rate;
When the SF6 and O2 gas content exceeds the standard, the fan will automatically start;
Intelligent Monitoring and Alarm System for SF6 Gas LeakageTimed exhaust function;
Activate the forced exhaust function when an alarm is triggered;
Relevant historical data storage and retrieval functions;
Temperature and humidity detection, alarm and display;
Voice prompt alarm function;
Main technical parameters
SF6 concentration over limit alarm point: 1000ppm, accuracy < ± 5%;
O2 concentration detection range 0-25%, oxygen deficiency alarm point: 18%, accuracy < ± 0.5%;
Temperature display range: -20~+99 ℃, accuracy < ± 0.5%;
Humidity display range: 0-99% RH, accuracy < ± 3%;
Input power supply: AC 220V ± 20%;
Alarm output contact power: AC 220/5A;
Fan output contact: 380V/15A (three-phase) or 220V/15A;
Fan startup: When the O2 content is ≤ 19.6% or the SF6 gas concentration is>1000ppm, the fan will automatically start, and the startup time will be automatically set according to the time period. The fan can be manually controlled or forced to start;
Massive alarm information storage design;
5-way high-capacity alarm contact output;
SF6 and O2 transmitters use imported original sensors with long service life;
SF6 gas detection alarm error<1%, oxygen alarm error<. 5%;
The fan controller can control the existing fan.
Technical Service
Our customer center provides online services and welcomes your inquiries and suggestions. Our professional technicians will patiently and meticulously answer every question you raise. We are extremely grateful for your valuable opinions and suggestions! For the products sold by our company, if needed, we will arrive at the site within 24 hours (within 500 kilometers, excluding transit time).