German VSE flowmeter spot instrument A350-28
AllFlow meter converter instrumentA350-28Flow meter wiring
Preparation before wiring
Tools and Materials
Prepare a cross screwdriver, wire stripping pliers, insulation tape, and multimeter (for detecting circuit continuity and voltage)
Confirm the flowmeter converterA350-28Match the model of the matching flowmeter and verify the voltage level on the equipment nameplate (e.gDC 24V)Signal type (such as4-20mAPulse signal and interface specifications (such asM12Circular connector or terminal block
Safety precautions
Disconnect the power supply before wiring to ensure that the equipment is in a power-off state and avoid electric shock or damage to the circuit
Check if the insulation layer of the cable is intact, without any damage or aging, and avoid damaging the core wire when stripping
Interface definition and pin description
A350-28Transformers are typically equipped with input interfaces (for connecting flow meter sensors) and output interfaces (for connecting control systems or display devices)
Input interface (flowmeter sensor connection)
pin1(VCC)The positive pole of the sensor power supply is usuallyDC 24V(Consistent with the power supply requirements of the flowmeter sensor)
pin2(GND)Negative pole of sensor power supply/Signal ground, shared with the negative pole of the power supply
pin3(SIG IN)Flow signal input, receiving pulse signals output by flow meter sensors (such asNPN/PNPType) or analog signal (corresponding mode needs to be selected according to the sensor type, set through the converter dip switch)
Output interface (control system connection)
pin4(4-20mA OUT+)Analog output positive pole, connectedPLC/DCSofAIModule positive pole
pin5(4-20mA OUT-)Analog output negative pole, connectedPLC/DCSofAIModule negative pole
pin6(PULSE OUT)Pulse signal output (optional), used for cumulative flow measurement, can be connected to a counter or pulse acquisition module (pulse type needs to be confirmed)NPNOpen collector orPNP)
pin7(ALARM)Alarm signal output (optional, normally closed)/Normally open (configurable), triggered when there is abnormal flow (such as over range, sensor failure), connectedPLCofDImodule
Wiring steps
Connection between flowmeter sensor and converter
step1Thread the flowmeter sensor cable through the waterproof joint and peel off the outer insulation layer (approximately)5cm)Expose the core wire (recommended core wire length)5-8mm)
step2According to the sensor pin definition (refer to the sensor manual), connect the positive terminal of the sensor power supply to the input interface pin of the converter1(VCC)Connect the negative terminal of the power supply to the pin2(GND)Connect the signal output line to the pin3(SIG IN)
step3Use a screwdriver to tighten the terminals, ensuring that the wiring is secure, without looseness or poor contact, and wrap the exposed core wire with insulating tape (if it is a non insulated terminal)
Converter and control system connection
step1Control the system (such asPLCofAIThe module cable is connected to the output interface of the converter,4-20mAPositive terminal pin4, negative terminal pin5If a pulse signal is required, connect the pulse acquisition line to the pin6; Alarm signal line pin connection7(Pay attention to distinguishing between normally open)/Normally closed contacts
step2Confirm the power input of the converter (usuallyDC 24V, PinL+andM)Connect the positive pole of the external power supplyL+Negative pole connectionMPlease note that the polarity cannot be reversed
Grounding treatment
The converter housing needs to be reliably grounded (through grounding terminals or screws), and the grounding resistance should be less than4ΩTo avoid electromagnetic interference affecting signal stability
Wiring inspection and debugging
Line continuity detection
Use a multimeter in the resistance range to check if the wires between each pin are conductive, and eliminate any open or short circuits (such asVCCandGNDThere should be insulation between them, and there should be no short circuit between the signal input line and the ground
Power and signal testing
Connect the power and observe the converter indicator light(POWERThe constant light indicates that the power supply is normal,SIGNALThe flashing light indicates that a traffic signal has been received
Connect the current range of the multimeter in series4-20mAIn the output circuit, check if the no-load current is4mAWhen there is no flow, manually push the impeller of the flowmeter, and the current should increase linearly with the increase of flow20mA(Full scale)
Parameter Configuration
Set the range through the converter button or upper computer software (such as0-100L/min)Signal type (pulse)/Simulate parameters such as flow meters and alarm thresholds to ensure compatibility with flow meters and control systems
Common Problems and Solutions
No signal output
Check if the sensor power supply is normal (pins)1and2The voltage between them should be24V)Whether the sensor cable is connected in reverse or has poor contact; Confirm if the dip switch of the converter is correctly set for the signal type (e.gNPN/PNPSelect)
The output signal fluctuates greatly
Check if the grounding is good and keep away from strong electromagnetic interference sources (such as motors and frequency converters); Check if the sensor is securely installed and if the impeller is stuck
Alarm triggered incorrectly
Re calibrate the alarm threshold to ensure it matches the actual working conditions; Check if there is any malfunction in the sensor (such as impeller wear or blockage), and clean or replace the sensor
Precautions
After the wiring is completed, organize the cables and secure them to avoid pulling and loosening the terminals; Waterproof measures should be taken during outdoor installation to ensure good sealing at the joints
Regularly check whether the wiring terminals are oxidized and whether the cables are aged during long-term use, and maintain them in a timely manner to ensure measurement accuracy
achievableAll A350 -28The correct wiring of converters and flow meters ensures stable transmission of flow signals to the control system, meeting the measurement and monitoring needs in industrial processes
VS0.1GP012V-32N11/4
VS1GP012V-32N11/4
VS4GP012V-32N11/6
VSI0.4/16GPO12V-32W15/4
Vsi2 / 16gpo54v-32n11 / 4
VSI0.04/16EPO12E42R11
German VSE flowmeter spot instrument A350-28
KRACHT Clark from Germany provides on-site selection and technical support for flow meters and indicators, and has competitive purchasing prices for gear pumps, valves, and spare parts
VSE Germany (flowmeter provides project selection and technical support)
In addition, there are many brands that also have advantages:
Beinlich Bailey pump (optional)
RICKMEIER pump (optional)
MTS sensor
TEMPOSONICS sensor
MEISTER flow switch
KOBOLD flowmeter, temperature switch
ATOS hydraulic solenoid valve, pump, pressure relay
WEBTEC flowmeter, flow indicator
HYDAC Hedec filters, filter cartridges, sensors
P+F Beckhoff sensor, safety barrier
HAWE hydraulic pump, hydraulic valve
VESTA Vesta cylinder, solenoid valve