Product Overview
The digital large-scale grounding resistance tester, also known as the power frequency grounding resistance tester, grounding resistance meter, etc., is a commonly used instrument for inspecting and measuring grounding resistance. It adopts a new type of variable frequency AC power supply, dual frequency measurement technology, ultra large touchable color screen, and microprocessor technology to meet the impedance requirements of two-wire, three wire, and four wire tests. At the same time, it can measure parameters such as soil resistivity, step voltage, distributed potential, contact voltage, and current phase angle. Suitable for telecommunications, power, meteorology, computer rooms, oil fields, power distribution lines, iron tower transmission lines, gas stations, factory grounding grids, lightning rods, etc., in compliance with the standards for testing instruments for power substations and lightning protection devices. The instrument testing is characterized by precision, speed, simplicity, stability, and reliability.
The maximum open circuit voltage output can reach 400V, and the maximum short-circuit current can reach 5A. The microprocessor control and automatic dual frequency technology can accurately measure and calculate the grounding impedance value at 50Hz power frequency under strong interference conditions, and the large screen display is clear at a glance. Simultaneously store 100 sets of data, with a resistance measurement range of 0.000 Ω to 2000 Ω. Measurement data can be printed out through a thermal printer.
Composed of a host, testing line, grounding rod, etc., it has functions such as historical data reading, viewing, saving, and printing.
technical parameters
Gong Gongcan |
Ground resistance measurement, soil resistivity measurement, step voltage measurement, distributed potential measurement, contact voltage measurement |
Range of grounding resistance |
0.000-2000 Ω Error: ± 2% rdg ± 5dgt |
Ground resistance resolution |
0.001Ω |
Rated measurement power |
2000W |
anti-interference capability |
Anti power frequency 50Hz voltage 50V |
Benchmark conditions |
23 ℃± 5 ℃, below 70% RH (auxiliary grounding resistance 20 Ω± 10%, ground voltage<10V) |
electricity source |
AC 220V 10A (50Hz) |
back light |
Adjustable backlight brightness |
measurement method |
Four wire test, three wire test, two wire test |
measurement method |
Grounding impedance: rated current method, |
Short circuit test current |
1A, 2A, 3A, 4A, 5A (5-speed setting) |
Range of electrode spacing for soil resistivity |
Can be set from 1m to 100m |
test frequency |
45Hz、55Hz、 Automatic dual band option |
Maximum short-circuit current |
AC 5A ± 10% sine wave |
Maximum no-load voltage |
AC 400V ± 10% sine wave |
display mode |
7-inch touch color screen |
touch screen |
is |
Measurement indication |
Measurement progress display, measurement prompt animation display |
Instrument size |
Length, width, and height: 540mm × 440mm × 210mm |
Standard test line length |
Red 15m, black 15m, yellow 10m, green 10m, yellow 1.5m, green 1.5m each |
auxiliary grounding rod |
800mm 2 pieces, 200mm 2 pieces |
measure time |
Grounding impedance: about 1 minute/time |
hit India |
Built in thermal printer |
Printing paper specifications |
57*40mm |
data storage |
100 sets, "Save successfully!" storage indication, displaying "Save failed, space is full!" character indicating storage is full |
data lookup |
have |
Overflow display |
Overscale overflow function: "OL" symbol display |
Auto Shutdown |
Nothing |
merit consume |
Standby:<110W |
Measurement: 2000W | |
quality quantity |
Instrument: 27 kg |
Test line, auxiliary grounding rod, instrument bag: 5.5kg | |
Working temperature and humidity |
-10℃~40℃; Below 80% RH |
Storage temperature and humidity |
-20℃~60℃; Below 70% RH |
insulation resistance |
Above 10M Ω (500V between circuit and casing) |
endure press |
AC 3700V/rms (between circuit and casing) |
electromagnetic properties |
IEC61010-4-3, Wireless frequency electromagnetic field ≤ 1V/m |
Suitable for safety regulations |
IEC61010-1、IEC1010-2-31、IEC61557-1,5、IEC60529(IP54)、 污染等2、 CAT Ⅲ 300V |