- Phone
-
Address
Room 312, No. 98, Mount Taishan East Road, Baoying County (Baiyue Power)
Yangzhou Baiyue Electric Co., Ltd
Room 312, No. 98, Mount Taishan East Road, Baoying County (Baiyue Power)
BYKG-JD High Voltage Switch Mechanical Characteristics Tester
BYKG-JD High Voltage Switch Mechanical Characteristics Tester
1. This device has12Road contact output, can simulate simultaneously12A high-voltage circuit breaker contact.
2The closing or opening time of the high-voltage circuit breaker can be1-9999.99mSSet arbitrarily within the scope.
3Resolution:10us.
4Accuracy:0.01%Reading ±10us.
5Bounce frequency can be selected1kHzThe2kHz.
6The number of bouncing pulses can be0-20 Set arbitrarily within a certain range.
7Support testing in different periods.
8Support internal triggering, external triggering, active triggering, and passive triggering.
9Ambient temperature10-30degree
10Environmental humidity: less than85%
BYKG-JD High Voltage Switch Mechanical Characteristics Tester
The circuit of the time calibration device is divided into: trigger circuit, high-speed pre-set counter circuit, high-precision crystal oscillation circuit, microcontroller control circuit, and output control circuit, as shown in the figure(1)As shown.

Figure(1)
The characteristics of this time calibration device are:
1Strong real-time performance, the device strives to achieve real-time triggering, real-time counting, and real-time output. In order to achieve real-time, a constant current trigger is used in the triggering stage, and a high-speed programmable logic circuit is used in the counting stage to form a synchronous counter, ensuring that the counting output is synchronized with the reference pulse. The output circuit is simulated using transistors.
2Adopting high-precision quartz crystal oscillator to ensure the accuracy and stability of the reference pulse.

Precautions for use:
1The pulse output mode of this device is used to test whether the instrument is accurate. It is required that the output terminal cannot be short circuited or connected to any other active output port. Otherwise, it is easy to damage the output terminal.
2When using the active internal trigger function, the active trigger terminal will have120The trigger voltage output should be around volts. Please note that the active trigger terminal should not be short circuited and should not be touched by hand.
System configuration:
1JST-2019Ahigh pressureCalibration device for switch dynamic characteristic tester a
2power cord a strip