- Phone
-
Address
Building 6, Optics Valley Electromechanical Industrial Park, No. 84 Gaoxin 5th Road, Donghu New Technology Development Zone, Wuhan City, Hubei Province
Wuhan Ultra High Voltage Power Technology Co., Ltd
Building 6, Optics Valley Electromechanical Industrial Park, No. 84 Gaoxin 5th Road, Donghu New Technology Development Zone, Wuhan City, Hubei Province
Meet the scope of the test sample
1、10kV/300mm2AC withstand voltage test for cable 1.5km, capacitance ≤ 0.5632 μ F, test frequency 30-300Hz, test voltage 22kV, test time 5min.
2、35kV/300mm2AC withstand voltage test for cable 0.35km, capacitance ≤ 0.0681 μ F, test frequency 30-300Hz, test voltage 52kV, test time 60min.
3. AC withstand voltage test of 35kV main transformer, capacitance ≤ 0.02 μ F, test frequency 45-65Hz, test voltage not exceeding 68kV, test time 1min.
4. AC withstand voltage test for electrical equipment such as 10kV switches, with a test frequency of 30-300Hz, a test voltage not exceeding 42kV, and a test time of 1 minute.
AC/DC power frequency withstand voltage test devicemajor component
| serial number | Device Name | Specification Model | unit | quantity |
| 1 | Variable Frequency Power Supply | UHV-4kW | platform | 1 |
| 2 | Incentive Transformer | UHV-4kVA/1.5/3/6kV/0.4kV | platform | 1 |
| 3 | High-voltage reactor | UHV-25kVA/25kV | section | 3 |
| 4 | Capacitive voltage divider | UHV-1000pF/80kV | set | 1 |
hand overDC power frequency withstand voltage test deviceMain technical parameters and functions
| Rated capacity | 75kVA |
| rated voltage | 25k; 75kV |
| rated current | 3A;1A |
| measurement accuracy | Effective value of the system at level 1.5 |
| operating frequency | 30-300Hz |
| Device output waveform | sine wave |
| Quality factors | The device itself has a Q ≥ 30 (f=45Hz) |
| waveform distortion rate | Output voltage waveform distortion rate ≤ 1% |
| input power | Single phase 220 or three-phase 380V voltage, frequency 50Hz |
| working hours | Under rated load, continuous operation for 60 minutes is allowed; Overvoltage 1.1 times for 1 minute |
| temperature rise | Temperature rise ≤ 65K after 60 minutes of continuous operation under rated load |
| protection function | Protection functions such as overvoltage, overcurrent, zero start, system detuning (flashover), etc |
| ambient temperature | -20℃-55℃ |
| relative humidity | ≤90%RH |
| altitude | ≤ 3000 meters |
Device capacity verification (device capacity is set at 75kVA, divided into three sections of reactors, with a single section of 25kVA/25kV/1A/110H). )
| serial number | experiment | Test frequency | Test current |
| 1 | 10kV/300mm2AC withstand voltage test for cable 1.5km, capacitance ≤ 0.5632 μ F, test frequency 30-300Hz, test voltage 22kV, test time 5min. If three reactors are connected in parallel, L=110/3=36.7H | f=1/2π√LC=1/(2×3.14×√36.7×0.5632×10-6)=35.01Hz | I=2πfCUtry=2π×35.01×0.5632×10-6×22×103=2.73A |
| 2 | 35kV/300mm2AC withstand voltage test for cable 0.35km, capacitance ≤ 0.0681 μ F, test frequency 30-300Hz, test voltage 52kV, test time 60min. Use three reactors in series (mutual inductance coefficient 1.2), L=110 × 3 × 1.2=396H | f=1/2π√LC=1/(2×3.14×√396×0.0681×10-6)=30.65Hz | I=2πfCUtry=2π×30.65×0.0681×10-6×52×103=0.68A |
| 3 | AC withstand voltage test of 35kV main transformer, capacitance ≤ 0.02 μ F, test frequency 45-65Hz, test voltage not exceeding 68kV, test time 1min. If three reactors are connected in series (with a mutual inductance coefficient of 1.2), then L=110 × 3 × 1.2=396H | f=1/2π√LC=1/(2×3.14×√363×0.02×10-6)=56.55Hz | I=2πfCUtry=2π×56.55×0.02×10-6×68×103=0.48A |
Equipment combination method during the experiment
| combination method Subject of the test sample | Reactor selection | Incentive Transformer | Test voltage |
| 10kV/300mm2Cable 1.5km | Use three parallel reactors | 1.5kV | ≤22kV |
| 35kV/300mm2Cable 0.35km | Use three reactors in series | 3kV | ≤52kV |
| AC withstand voltage test of 35kV main transformer | Use three reactors in series | 6kV | ≤68kV |
| 10kV switches and other electrical equipment | Use three reactors in series | 3kV | ≤42kV |
System configuration parameters
(1) Variable frequency power supply UHV-4kW (1 unit)
| Rated output capacity | 4kW |
| working power supply | 220/380 ± 10% V (single/three-phase), power frequency |
| output voltage | 0-400V |
| Rated input current | 10A |
| Rated output current | 10A |
| voltage resolution | 0.01kV |
| Voltage measurement accuracy | 1.5% |
| Frequency adjustment range | 30-300Hz |
| Frequency adjustment resolution | ≤0.1Hz |
| frequency stability | 0.1% |
| runtime | Continuous 60 minutes at rated capacity |
| Component temperature during continuous operation for 60 minutes at rated capacity | ≤65K |
| noise level | ≤50dB |
| Dimensions (length, width, height mm) | 400×280×400 |
| weight | About 10kg |
(2) Excitation transformer UHV-4kVA/1.5/3/6kV/0.4kV (1 unit)
| Rated capacity | 4kVA |
| input voltage | 0-400V |
| output voltage | 1.5/3/6kV |
| structure | dry-type |
| Dimensions (length, width, height mm) | 450×330×430 |
| weight | About 45kg |
(3) High voltage reactor UHV-25kVA/25kV (3 sections)
| Rated capacity | 25kVA |
| rated voltage | 25kV |
| rated current | 1A |
| inductance | 110H/single section |
| Quality factors | Q≥30(f=45Hz) |
| structure | dry-type |
| Size (inner diameter height mm) | ∅282×435 |
| weight | About 45kg |
(4) Capacitive voltage divider UHV-1000pF/80kV (1 set)
| rated voltage | 80kV |
| High voltage electrical capacity | 1000pF |
| Dielectric loss | tgσ≤0.5% |
| voltage division ratio | 1000:1 |
| measurement accuracy | Effective value level 1.5 |
| Size (inner diameter height mm) | ∅140×1000 |
| weight | About 8kg |
Supply List
| serial number | Device Name | Model and Specifications | unit | quantity |
| 1 | Variable Frequency Power Supply | UHV-4kW | platform | 1 |
| 2 | Incentive Transformer | UHV-4kVA/1.5/3/6kV/0.4kV | platform | 1 |
| 3 | High-voltage reactor | UHV-25kVA/25kV | section | 3 |
| 4 | Capacitive voltage divider | UHV-1000pF/80kV | set | 1 |
| 5 | Internal connection line | set | 1 | |
| 6 | Factory inspection report | copy | 1 | |
| 7 | User Manual | copy | 1 | |
| 8 | Product Qualification Certificate | copy | 1 | |
| 9 | Packing List | copy | 1 |
Reference experimental standards
| DL/T 596-1996 | Preventive Testing Regulations for Power Equipment |
| GB50150-2016 | Standard for Handover Test of Electrical Equipment in Electrical Installation Engineering |
| GB10229-88 | Reactor |
| GB1094 | Power Transformers |
| GB1094.1-GB1094.6-96 | Degrees of Protection Provided by Enclosures |
| GB2900 | Electrical Terminology and Terminology |
| GB/T16927.1~2-1997 | High Voltage Test Technology |
| DL/T474.4-2006 | Guidelines for on-site insulation testing - AC withstand voltage test |
| DL/T1015 | Guidelines for the use of voltage measurement systems for on-site DC and AC withstand voltage tests |
| GB/T311.1-1997 | Insulation and Coordination of High Voltage Transmission and Transformation Equipment |
| GB191-2000 | Packaging, Storage, and Transportation Symbols |
| JB/T9641-1999 | Test Transformer |
| IEC358(1990) | Coupling capacitors and capacitive voltage dividers |
| GB4793-1984 | Safety Requirements for Electronic Measuring Instruments |
| GB/T3859.2-1993 | Guidelines for the Application of Semiconductor Inverters |
| GB/T2423.8-1995 | Basic Environmental Testing Regulations for Electrical and Electronic Products |
| DL/T849.6-2004 | General technical specifications for specialized testing instruments for power equipment - Part 6: High voltage resonance test apparatus |
Note:
1. The appearance of the product is subject to the actual product. Technical parameters and models are subject to change without prior notice. If there is any act of theft or copying, legal responsibility will be pursued.
2. For more information on ultra-high voltage products, please enter the product center.








workshop floor
The ultra-high voltage self owned factory covers an area of 4500 square meters and has a total of more than 100 employees. The series resonance device is widely used in industries such as power, metallurgy, petroleum, and chemical. It is suitable for the interconnection and preventive testing of large capacity, high-voltage capacitive samples such as power cables, power transformers, hydroelectric generators, GIS, etc.











Product Portfolio
Product Attachment Diagram

complete set

Incentive Transformer

Variable Frequency Power Supply

reactor

voltage divider

Voltage divider signal line

power cord

Reactor series parallel line

Reactor series parallel line

Variable frequency source output line

High voltage output line

Incentive variable output line

ground wire

Specialized testing line crocodile clip

Specialized testing line pliers

USB drive
Product detail images

Incentive Transformer

Incentive Transformer Panel

Excitation transformer input

Excitation transformer terminal

Variable Frequency Power Supply

Variable frequency power supply display screen

Variable frequency power input

Variable frequency power supply grounding

Variable frequency power printer

Variable frequency power supply USB interface

Variable frequency power switch