- Phone
-
Address
Shanghai Baoshan District Industrial Park, Hutai Road
Shanghai Runliu Electric Co., Ltd
Shanghai Baoshan District Industrial Park, Hutai Road
The ZGF-300kV/2mA portable DC high voltage generator meets the technical requirements of the national standard and industry standard ZBF24003-90 "General Technical Conditions for Portable DC High Voltage Generators", and is suitable for on-site testing of various high-voltage electrical appliances in the power sector, including zinc oxide lightning arresters, DC withstand voltage and leakage tests of power cables. Also used as a power source for electrostatic suction, spraying, and other applications.
Portable DC High Voltage GeneratorUsing pulse width modulation (PWM) technology IGBT、 And the incoming electronic circuits and components have output that is not affected by power grid fluctuations, and have protection measures such as zero position, overcurrent, breakdown, and overvoltage. Regardless of overcurrent, breakdown, or overvoltage protection circuits, they can quickly operate, effectively ensuring the safety of equipment and personnel. Its output adopts LCD display, which is much lighter in size and weight than the original KGF type, making it very suitable for on-site use. The newly designed "0.75U" LCD display can directly display and latch 0.75U1mA for on-site testing without manual calculation.
Portable DC High Voltage GeneratorIt has the advantages of small size, high power, light weight, easy to carry, convenient operation, safety and reliability.
Portable DC High Voltage GeneratorProduct specifications and technical indicators
Output rated voltage and current |
60kV/2mA |
60kV/10mA |
120kV/2mA |
120kV/5mA |
200kV/2mA |
200kV/5mA |
300kV/2mA |
|
Control box Weight |
4.5kg |
4.5kg |
4.5kg |
4.5kg |
4.5kg |
4.5kg |
4.5kg |
|
Pressure multiplier Size and weight |
Φ120×300mm 4.1kg |
Φ148×360mm 4.5kg |
Φ120×450mm 5.5kg |
Φ148×500mm 6.2kg |
Φ148×730mm 11kg |
Φ148×760mm 11.5kg |
Φ180×1100mm 20kg |
working power supply |
50Hz; 220V±10% |
||||||
measurement error |
Digital voltmeter: 1% (full degree) ± 1 word; Digital ammeter: 1% (full scale) ± 1 word |
||||||
Stability |
Random fluctuations, when the power supply changes by ± 10%, ≤ 0.5% |
||||||
ripple factor |
≤ 0.5% (full degree) |
||||||
working method |
Intermittent use, rated load for 60 minutes |
||||||
working environment |
Environmental temperature: -15 ℃ to 50 ℃; Relative humidity:<90% (no condensation); Altitude: < 2500m |
||||||