Net Safety's UV/IRS flame detectors have excellent performance and offer a variety of outstanding features and characteristics. Sensors tuned with UV/IRS precision must recognize and confirm two precise radiation spectra in order to trigger a fire condition. This kind of essence
Net Safety's UV/IRS flame detectors have excellent performance and offer a variety of outstanding features and characteristics. Sensors tuned with UV/IRS precision must recognize and confirm two precise radiation spectra in order to trigger a fire condition. This precise and reliable flame monitoring technology combined with immunity to arc welding, object thermal radiation, lightning, and sunlight can significantly reduce costly false alarms, while providing important safety protection for your premises and personnel.
The Net Safety UV/IRS flame detector is packaged in a sturdy explosion-proof enclosure and utilizes the latest modular microprocessor and UV/infrared sensor technology to achieve precise and reliable monitoring of hydrocarbon flames. It can run independently or connect to various networked security systems to establish a reliable flame monitoring system.
UV/IRS flame detectors have multiple unique features that make them the best in the industry: extremely wide field of view - up to 120 degrees; User defined sensitivity and time delay settings can be completed on-site without the need for specialized tools; One of the lowest power consumption levels and widest voltage ranges on the market; Provide basic independent HART communication interface selection.
The excellent UV/IR flame detector designed by Net Safety is easy to operate and maintain, while meeting all the safety and performance requirements for high-risk industrial installations!
Sending an alarm requires two types of radiation sources - minimizing false alarm events to the greatest extent possible
The field of view can reach 120 degrees - each detector has a wide coverage range
Class I Zone 1 Explosion proof Certification - Suitable for Hazardous Areas
Low power consumption, wide voltage range - overall low cost, no need to consider voltage drop issues
Multiple output options - analog, relay, digital RS485 Modbus RTU protocol, HART communication protocol, and optional ground state HART controller input
Indoor and outdoor direct connection or connection to a maximum distance of 2000 feet - flexible installation
Not affected by lightning, arc welding, sunlight, and object thermal radiation - avoid false alarms caused by nearby activities
Adjustable rotary installation - simplifies installation and reduces costs
User programmable sensitivity and time delay settings - fine-tuning performance suitable for specific applications
Multi color high brightness LED - on-site visual detector status
Manual and automatic testing of optical surfaces - facilitates the development of maintenance plans by evaluating cleanliness
Monitoring timer can monitor internal electronic components - continuous system self diagnosis
UV/IRS (infrared/ultraviolet)
Part number: UV/IRS-XXX-X-X-X-X-X-X-X
Response time:<6 seconds (depending on fuel source, flame size, distance)
Field of view: Horizontal 120 degrees/Vertical 95 degrees
Spectral range: 185 to 260 nanometers (1850 to 2600 angstroms) UV radiation | Infrared radiation in the 4.4 micron range
Sensitivity settings: High/Medium High/Medium/Low (can be selected on-site through a dimmer switch)
Time delay: 0, 3, 5, 7 seconds (can be selected on-site through the dimmer switch)
Temperature: -50 ° C to+75 ° C (-58 ° F to 167 ° F)
IP/NEMA rating: IP66- NEMA 4X
Material: Aluminum or 316 Stainless Steel
Voltage range: 10-32 VDC
Power consumption: Analog model - nominal 1.1W/maximum 2.76W (@ 24VDC)
Relative humidity: 0-95%, no condensation
Warranty period: 3 years for electronic components/2 years for sensors