- Phone
-
Address
Building 6, Optics Valley Electromechanical Industrial Park, No. 84 Gaoxin 5th Road, Donghu New Technology Development Zone, Wuhan City, Hubei Province
Wuhan Ultra High Voltage Power Technology Co., Ltd
Building 6, Optics Valley Electromechanical Industrial Park, No. 84 Gaoxin 5th Road, Donghu New Technology Development Zone, Wuhan City, Hubei Province
| output current | ≥1A,3 通道 |
| data sampling | Sampling channels: 6 channels |
| Sampling frequency: 10kHz/s | |
| measurement range | Transition resistance: 0.5 Ω~20 Ω |
| Transition time: ≤ 250ms | |
| resolution | Resistance: 0.01 Ω |
| Time: 0.1ms | |
| measurement accuracy | Transition resistance: ± (5%+3 characters) |
| Transition time: ± (0.1%+1 word) | |
| storage method | USB storage, 1GB local storage |
| Overall dimensions | 350mm×230mm×200mm |
| host weight | 5kg |
| ambient temperature | -10℃~50℃ |
| ambient humidity | ≤85%RH |
| working power supply | AC220V±10% |
| power frequency | 50±1Hz |
1. Vertical chassis structure, lightweight and easy to carry.
2. Transformer on load tap changer testerBuilt in embedded PC-104 industrial control computer, fast speed and large storage capacity
3. Transformer on load tap changer testerBuilt in precision constant current source with * reliable protection circuit
4. 6-channel high-speed synchronous data sampling
5. 5.7-inch backlit wide temperature LCD with clear display under sunlight
6. Display results of graphics and text
7. T9 input method, capable of inputting numbers, letters, Chinese characters, and various symbols
8. The host has a storage capacity of 1G and can store tens of thousands of sets of test data
9. Equipped with external USB storage function to store more data
10. USB data synchronization function, convenient data exchange
11. Tree based storage structure, stored by station name, number, and tap position for easy data retrieval
12. Built in panel thermal printer
The on load tap changer is a moving component connected to the transformer circuit, so the detection of on load tap changers is becoming increasingly important. According to the industry standard "DL/T846.82004 Load tap changer tester", it is required to check the action sequence of the load tap changer, measure the switching time, etc. To this end, our company has successfully developed a transformer on load tap changer tester. The transformer on load tap changer tester is mainly used to measure the transition waveform, transition time, instantaneous transition resistance value, three-phase synchronicity, etc. of the transformer on load tap changer.
The instrument has a high degree of intelligence, with all Chinese menu prompts and simple operation. The instrument is small in size, light in weight, and has strong anti-interference ability, greatly reducing the labor intensity of on-site workers. It is an ideal instrument for power generation units and transformer manufacturing industries to ensure safe production and improve product quality.