Welcome Customer !

Membership

Help

Wuhan Ultra High Voltage Power Technology Co., Ltd
Custom manufacturer

Main Products:

instrumentb2b>Products

Wuhan Ultra High Voltage Power Technology Co., Ltd

  • E-mail

  • Phone

  • Address

    Building 6, Optics Valley Electromechanical Industrial Park, No. 84 Gaoxin 5th Road, Donghu New Technology Development Zone, Wuhan City, Hubei Province

Contact Now

High frequency DC high voltage generator

NegotiableUpdate on 05/06
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

The high-frequency DC high voltage generator adopts a high-frequency voltage doubling circuit and applies * PWM pulse width modulation technology to improve the power supply adjustment rate and load adjustment rate, resulting in high voltage stability and low ripple. Using imported high-power IGBT devices and their driving technology to eliminate switch interference and achieve high quality and portability of high-voltage generators. Selecting imported high-frequency and high-voltage rectifier diodes makes the voltage doubler more compact and lightweight, improving the overall efficiency of the machine. According to the theories of EMI electromagnetic interference and EMC electromagnetic compatibility, measures such as shielding, isolation, and grounding are adopted to enhance the safety of the entire machine and withstand rated voltage discharge without damage.

Product Details

Scope of application
  • 1. Conductivity current test of valve type lightning arrester.

  • 2. DC withstand voltage test and leakage current measurement of power transformers.

  • 3. DC withstand voltage test and leakage current measurement of high-voltage cables (35-500kV and below).

  • 4. U1mA DC reference voltage test and 0.75U1mA leakage current test for zinc oxide lightning arrester.

Product parameters

technical parameters

specification 60/2 60/3 60/5 120/2 120/3 120/5
Rated voltage (kV) 60 60 60 120 120 120
Rated current (mA) 2 3 5 2 3 5
Rated power (W) 120 180 300 240 360 600
Whole machine weight (kg) 9 10
Overall volume (mm)3 465*390*190 565*390*190
Height of pressure doubling cylinder (mm) 440 535
Output voltage accuracy ± (1.0% reading ± 2 words)
Output current accuracy ± (1.0% reading ± 2 words)
ripple factor ≤0.5%
working method Intermittent use, rated load for 30 minutes
overload capacity The no-load voltage can exceed the rated voltage by 10% and be used for 10 minutes
The maximum charging current is 1.25 times the rated current
Power supply: AC220V ± 10% 50Hz
working environment Temperature: -10-40 ℃
Relative humidity: not exceeding 85% at room temperature of 25 ℃ (no condensation)
Altitude: below 1500 meters

Selection reference

Selection Reference - Zinc Oxide Surge Arrester DC Reference Voltage and Leakage Current Test

Rated voltage of lightning arrester (kV) 10 35 66 110 220
DC reference voltage kV 28 90 135 168 314
Equipment selection kV/mA ZGF - 60 / 2 ZGF - 120 / 2 ZGF - 200 / 2 ZGF - 200 / 2 ZGF - 400 / 3

Selection reference - choose according to the voltage level of the substation

Substation voltage level kV 10 35 66 110 220 330
Maximum test voltage kV 47 105 135 192 305 Greater than 400
Equipment selection kV/mA ZGF - 60 / 2 ZGF - 120 / 2 ZGF - 200 / 2 ZGF - 200 / 2 ZGF - 400 / 3 ZGF - 800 / 10

Selection reference - choose based on the qualification level of repair and testing

Maintenance and testing level Level 5 Level 4 Level 3 Level 2 Level 1
Maximum test voltage kV 28 90 168 305 Greater than 400
Equipment selection kV/mA ZGF - 60 / 2 ZGF - 120 / 2 ZGF - 200 / 2 ZGF - 400 / 3 ZGF - 800 / 10

Selection reference - DC withstand voltage and leakage current test of paper insulated cable

Rated voltage of cable Uo/U kV 3.6 / 6 6 / 6 6 / 10 8.7 / 10 21 / 35 26 / 35
DC test voltage kV 17 30 40 47 105 130
Equipment selection kV/mA ZGF - 60 / 2 ZGF - 60 / 2 ZGF - 60 / 2 ZGF - 60 / 2 ZGF - 120 / 3 ZGF - 200 / 5

Selection reference - Rubber insulated cable DC withstand voltage and leakage current test

Rated voltage of cable Uo/U kV 6 / 10 8.7 / 10 21 / 35 26 / 35 48 / 66 64 / 110 127 / 220
DC test voltage kV 26 37 63 78 144 192 305
Equipment selection kV/mA ZGF - 60 / 2 ZGF - 60 / 2 ZGF - 120 / 5 ZGF - 120 / 5 ZGF - 200 / 5 ZGF - 200 / 10 ZGF - 400 / 5

Selection reference - DC withstand voltage and leakage current test for main insulation of self accommodating oil filled cable

Rated voltage of cable Uo/U kV 48 / 66 64 / 110 127 / 220 190 / 330 290 / 500
DC test voltage kV 175 275 475 585 775
Equipment selection kV/mA ZGF - 200 / 3 ZGF - 300 / 3 ZGF - 500 / 5 ZGF - 600 / 5 ZGF - 800 / 10
Product features
  • 1. Stable output voltage:High frequency DC high voltage generatorBy using high-frequency voltage doubling circuit, applying new PWM pulse width modulation technology and voltage current dual loop feedback technology, the power supply adjustment rate and load adjustment rate are improved, resulting in high voltage stability and low ripple.

  • 2. Comprehensive protection: It has complete protection functions, including zero protection, overvoltage protection, overcurrent protection, and breakdown protection. The protection circuit uses nanosecond level dedicated sensors, which act quickly and reliably, effectively ensuring personal and equipment safety.

  • 3. 0.75U Function: An intelligent high-precision 0.75U function button is added. Pressing this button will automatically switch the voltage and current to the 0.75U state, which is beneficial for testing zinc oxide lightning arresters.

  • 4. Zero to zero boost: The boost potentiometer uses an imported multi turn potentiometer for zero to zero boost, ensuring a smooth boost process and high adjustment accuracy.

  • 5. Overvoltage setting: The overvoltage setting uses a digital dip switch, which is easy to operate and has high setting accuracy.

  • 6. Integrated design: Adopting an integrated design scheme, the host and the pressure doubler are placed in one chassis. Imported high-frequency and high-voltage rectifier diodes are selected to make the voltage doubler compact in size, improve overall efficiency, and facilitate portability.

  • 7. Reliable performance: High performance imported components are selected for key components, and special insulation materials are coated on the surface of the pressure doubling cylinder, which has good electrical performance, strong moisture resistance, and no leakage.

  • 8. Easy to operate:High frequency DC high voltage generatorThe layout of each functional button on the interface is reasonable, the instructions are clear, and it is easy to learn and use.

高压发生器高压发生器高压发生器高压发生器高压发生器高压发生器高压发生器高压发生器