Net Safety's single UVS flame detector can perform high-performance testing and meet strict industrial performance requirements. Our advanced UV sensors must recognize and confirm the precisely tuned radiation spectrum in order to initiate a fire condition, but for incandescent or fluorescent lamps
Net Safety's single UVS flame detector can perform high-performance testing and meet strict industrial performance requirements. Our advanced UV sensors must recognize and confirm a precisely tuned radiation spectrum in order to initiate a fire condition, but they do not respond to incandescent or fluorescent lamps, heaters, or sunlight, thus significantly reducing false alarms. Single UVS is designed for simple installation and low maintenance cost applications, while providing excellent safety performance.
Single UVS is encapsulated in a sturdy explosion-proof casing, utilizing the latest modular microprocessor and UV sensor technology to achieve precise and reliable monitoring of hydrocarbon and metal flames.
It can operate independently or be connected to various control devices to form a reliable flame monitoring system. Users can define sensitivity and time delay settings, and the built-in test routine ensures its continuous operation.
The field of view of a single UVS can reach 120 degrees and can be configured with analog, relay, and HART protocol outputs, including a low-power 10-32 Vdc wide voltage range.
The excellent UV flame detector designed by Net Safety is easy to operate and maintain, while meeting all the safety and performance requirements for high-risk industrial installations!
The field of view can reach 120 degrees - each detector has a wide coverage range
Class I Zone 1 Explosion proof Certification - Suitable for Hazardous Areas
Low power consumption, wide voltage range - overall low cost, no need to consider voltage drop issues
Multiple output options - analog, relay, digital RS485 Modbus RTU protocol, HART communication protocol, and optional ground state HART controller input
Indoor and outdoor direct connection or connection to a maximum distance of 2000 feet - flexible installation
Not affected by sunlight and object thermal radiation - avoid false alarms caused by nearby activities
Adjustable rotary installation - simplifies installation and reduces costs
User programmable sensitivity and time delay settings - fine-tuning performance suitable for specific applications
Multi color high brightness LED - on-site visual detector status
Manual and automatic testing of optical surfaces - facilitates the development of maintenance plans by evaluating cleanliness
Monitoring timer can monitor internal electronic components - continuous system self diagnosis
UVS (ultraviolet)
Part number: UVS-XXX-X-X-X-X
Response time:<6 seconds (depending on fuel source, flame size, distance)
Field of view: Horizontal 120 degrees/Vertical 95 degrees
Spectral range: 185 to 260 nanometers (1850 to 2600 angstroms) ultraviolet radiation
Sensitivity settings: High/Medium High/Medium/Low (can be selected on-site through a dimmer switch)
Time delay: 0, 3, 5, 7 seconds (can be selected on-site through the dimmer switch)
Temperature: -50 ° C to+75 ° C (-58 ° F to 167 ° F)
IP/NEMA rating: IP66- NEMA 4X
Material: Aluminum or 316 Stainless Steel
Voltage range: 10-32 VDC
Power consumption: Analog model - nominal 1.1W/maximum 2.76W (@ 24VDC)
Relative humidity: 0-95%, no condensation
Warranty period: 3 years for electronic components/2 years for sensors