Welcome Customer !

Membership

Help

Wuhan Hertz Power Equipment Co., Ltd
Custom manufacturer

Main Products:

instrumentb2b>Products

Wuhan Hertz Power Equipment Co., Ltd

  • E-mail

  • Phone

  • Address

    Building 22, Science and Technology Innovation Center, No. 20 Chuanggu Road, Dongxihu District, Wuhan City

Contact Now

Simulated Circuit Breaker Device III

NegotiableUpdate on 05/09
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

The simulated circuit breaker device III is mainly used for the whole set test of relay protection devices, as well as replacing real circuit breakers in other test projects, as a substitute equipment for actual circuit breakers in the transmission test of relay protection and automatic device with switch whole set systems; Accurate, reliable, and unlimited number of actions can greatly improve the correctness and completeness of the test, minimize the actual number of actions of the circuit breaker, and improve its service life.

Product Details

1.Device Overview

Simulated Circuit Breaker Device IIIMainly used for whole set testing of relay protection devicesAnd replacing real circuit breakers in other experimental projects,As a substitute equipment for the actual circuit breaker during the transmission test of the relay protection and automatic device with switch assembly systemAccurate, reliable, and unlimited number of actions can greatly improve the correctness and completeness of the test, minimize the actual number of actions of the circuit breaker, and improve its service life.Simulated Circuit Breaker Device IIIcan be paired withUsed in conjunction with relay protection verification deviceIt can also be used independentlyEspecially in the case of newly built factories or stations where the high-voltage circuit breakers are not properly adjusted or the DC power supply is not connected, using this device for relay protection testing will not be affected by external factors, thereby shortening the debugging time and improving the efficiency of the testing work. The use of this device in manufacturers and research departments is more efficient and effective. Other similar applications can be handled on a case by case basis.

2.Main Features

1)Provide a fully isolated DC systemadjustablePower supply, and there isheaderDisplay the adjusted voltage value;

2)Simultaneously providethreegroupdivideClose and lock the wire coil;

3)Comes with manual functiondivideClosing function;

4)divideThe resistance value of the closing coil can be adjusted in multiple levels;

5)divideThe closing exit time can be selected in multiple time periods;

6)Comes with multiple pairsdivideOpen contact output at the closing position;

7)Comes with multiple pairs of open/close pulse output empty nodes

8)Single chip microcomputer control system, capable of intelligent upgrading to meet various needs;

9)A high-performance hardware platform with industrial grade standard main components ensures the high quality of the device.

3.Main technical parameters

1)Working power supply voltageAC220V ± 10% 50HZ working current is less than 0.5A.

2)Output quantity node:Circuit breaker position output contact6Yes, they are independent of each other. Divided into two groups, corresponding to the circuit breaker trip coil additional3 pairs of closing and 3 pairs of opening pulse terminals.

3)divideVoltage for closing operationDC 40-250Vadjustable.

4)divideClose the switchtime10mS-1000mS can be set arbitrarily,error does not exceed±5ms。

5)divideClosing currentCoil resistance∞ΩThe880Oh,440Oh,220Oh,110ΩThe44Ω

6)manualdivideclose the circuitWhen passingtouch screenonManual closing "and" Manual closing "dividegate”Button to operate

Time circuit breaker simulation devicedivideThere is no current passing through the closing coil.

7)Output nodeContact capacity: DC220V/0.5A,AC220V/5A.

8)Opening and closing pulse output: provides three sets of outputsA 500 millisecond switch node.

9)DivideThe closing currents are0A、0.25A、0.5A、1A、2A、5AWhen the tripping and closing pulse is11At 0V, the correspondingdivideThe tripping and closing currents are respectively0A、0.125A、0.25A、0.5A、1A、2.5A !