Welcome Customer !

Membership

Help

Shanghai Xuji Electric Co., Ltd
Custom manufacturer

Main Products:

instrumentb2b>Products

Shanghai Xuji Electric Co., Ltd

  • E-mail

    sute@56412027.com

  • Phone

    13818304481,13917842543

  • Address

    508, Building 4, Lane 680, Shuishe West Road, Baoshan District, Shanghai

Contact Now

SMN-1 ABB drawer switch cabinet contact clamping force tester

NegotiableUpdate on 12/11
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

SMN-1 ABB drawer switch cabinet contact clamping force tester, using 5V0 constant voltage, using 5V0 constant voltage excitation to supply power to 1-5K pressure sensing resistor bridge, and collecting data from an external 24 bit high-precision A/D under the same 5V0 reference. Select various measurement methods from the bilingual prompt software menu in both Chinese and English. After data processing, it is displayed on a high brightness green 12864 dot matrix active light-emitting OLED screen. And there is a buzzer reminder and dedicated green and red OK and OUT lights to indicate whether the output result is qualified or not. It is a specialized measuring instrument used to check whether the contact pressure of power equipment is qualified.

Product Details

SMN-1 ABB drawer switch cabinet contact clamping force tester

SMN-1 ABB抽屉开关柜触头夹紧力测试仪

I. Overview

Due to the maximum application range of various low-voltage switchgear equipment in the power system, especially outdoor switches that operate in atmospheric environments and are exposed to weather conditions for a long time, the operating conditions are relatively harsh, and it is easy to cause mechanical and electrical failures. Especially, the contact contact part is corroded by the gas, which can lead to poor contact and heat generation. The contact pressure spring is annealed due to heat generation, resulting in a vicious cycle of contact heating and ultimately burning out the contacts, leading to accidents. During maintenance, only the obviously failed and broken contacts are often replaced, and the spring contacts with reduced pressure cannot be compared and replaced. Therefore, in long-term operation, the distribution of current in each contact will be different due to different pressures. The greater the difference, the more uneven the current distribution. Poor contact of one contact will affect the entire switch. The normal operation of the cabinet, Causing accidents to electrical equipment in operation.

The SMN series contact pressure detector uses 5V0 constant voltage excitation to power the 1-5K pressure sensing resistor bridge, and data is collected by an external 24 bit high-precision A/D under the same 5V0 reference. Select various measurement methods from the bilingual prompt software menu in both Chinese and English. After data processing, it is displayed on a high brightness green 12864 dot matrix active light-emitting OLED screen. And there is a buzzer reminder and dedicated green and red OK and OUT lights to indicate whether the output result is qualified or not. It is a specialized measuring instrument used to check whether the contact pressure of power equipment is qualified.

Instrument working mode:

Divided by settingsCalculate the contact pressure of the measurement display using three methods: "key measurement", "automatic", and "continuous".

Startup byCompare the comparison type and upper and lower limits of 24LC64 loaded into RAM to determine if the contact pressure is qualified.

If qualified, the buzzer will sound continuously0.5 seconds and the OK green light stays on, and the measurement value is displayed on the main screen.

If it is not qualified, the buzzer will beep three times rapidly and brieflyThe OUT red light is constantly on to sound an alarm, and the measurement value is also displayed on the main screen.

2、 Product Features

1. Multi functional display screen

2. Convenient bilingual four key operation interfaceAnd it can be measured with a dedicated one touch key.

3. Freely customizable measurements and judgments定方式

4.Concise calibration method

3、 Technical indicators

The main technical specifications of the SMN series contact pressure detector are:

Tension measurement(N)

Charging time

working hours


0~200N

shortest8 hours

shortest8 hours

scope

1.0 %

maximum12 hours

maximum24 hours

precision


SMN-1 ABB drawer switch cabinet contact clamping force tester

4、 Description of each functional component

SMN-1 ABB抽屉开关柜触头夹紧力测试仪


5、 Parameter settings

1.Working interface of the detector See Figure 1

The working interface of the integrator includes five interfaces, the first screen is the main interface, and the second screen is the auxiliary interface.

The main screen interface is shown in Figure 1:

SMN-1 ABB抽屉开关柜触头夹紧力测试仪

The measurement result is generated by pressing the test button or inserting the probe in automatic mode, and the result is displayed approximately every 3 seconds in continuous mode.

The zero point calibration of the second screen is shown in Figure 2:

SMN-1 ABB抽屉开关柜触头夹紧力测试仪


When the test head is empty and not loaded, enter the password "10" to complete the on-site zero calibration and reset to 0.

The auxiliary interface of the third screen is shown in Figure 3:

SMN-1 ABB抽屉开关柜触头夹紧力测试仪

Enter password22”Or“33”You can enter the user or engineer menu separately.

2. Display of working status

After the power switch is turned on, the instrument first performs a self check and enters the screen after completion1The work master displays the status.

2.Switching between work screens

press < Key orSwitch between the main work screen 1 and the auxiliary work screens 2 and 3 with the "+" symbol.

2.2-button measurement method

pressAfter pressing the "Test" button, clear the screen values and results and turn off the traffic lights. Then, perform a set of sampling calculations and comparisons, and display the new measurement results after a delay of 0.5 seconds.

2.5 Parameter Settings

On the display screen3 status, text prompt "Enter password", use "S,+",Enter the password using the "E" key combination.

E "key: Enter the initial password input state. S "key: Cancel input mode and return to the main screen display.

Press in input mode+”Press the key to cycle through the values 0-9 and symbols at the cursor.

Press in input mode<”Press the key to move the current input cursor position.

Press in input modePress the "E" key to bring up the cursor or confirm saving parameters.

If it is correct, enter the menu; if it is incorrect, return to the initial input state.

Zero point return0 Password: 10

User menu password: 22

Engineer menu password:33

6、 Instrument calibration and production settings

1.Tester menu

The detector menu includes a user menu, an engineer menu, and a manufacturing menu. The engineer menu must be set by operators with professional knowledge. The production and manufacturing menu is calibrated by the factory when the detector is sent out. After leaving the factory, this type of parameter setting can only be modified under the corresponding equipment conditions, otherwise it will cause measurement errors or failure of the detector!

In the menu browsing, pressPress the "+" key to scroll down; Press“<”Flip up the key. Press the "S" key to return to the work screen 2 interface. In the submenu, press the "S" key to exit; Press the "E" key to enter the modification mode. If you want to modify the selection item in the modified state, press the "+" key to select downwards; Press“<”Select upwards and press the "E" key to confirm. If it is an input based modification, follow theInput operationconduct.

name call, name, say, weigh

inside Rong

prepare note

fuck

make, do, create, compose, write, etc.

key

S

back button

·When setting parameters, it is used to exit the menu step by step

Return to the previous menu

Set value increase key

·When setting parameters, it is used to increase the current value of the cursor

·Switch display screen

Short parameters can be directly modified, long parameters can be pressed firstE 。0 →1→→9→.0Y→N→Y,+→-→+

Shift key

·Move the cursor left or right by one position

·Move right to increase the number of digits

·Switch display screen

Move left to skip the decimal point and return to the right when reaching the left end of the numerical range

E

confirm button

·Modify parameter settings

·When setting parameters, it is used to start inputting, confirming, and storing new parameter values

Long parameter first pressAfter entering E, clear the parameter and start inputting. Press E again to input the value and store it in EEPROM. Return the cursor to the far right end

Notes:

When setting parameters, the displayed content needs to be adjusted according toOnly after confirming with the "E" key can it be stored, otherwise the setting is invalid

2.Zero to zero

Zero point return0

F=0:ADJ ZERO

password:

Password:

XX

On site school sensor0-point ADZ

(Password)10)

Enter passwordAt 10 o'clock, calibrate the current AD value to the zero point ADZ

Enter passwordAt 90 o'clock, return to zero and clear to zero

3. User menu

In the auxiliary interface password input state, enterThe password "22" enters the user menu, and the user menu structure is shown in the following figure,

The functions and parameter meanings of each menu are shown in the following table:

table 1User parameter setting menu (The password is22).

table 2 User menu structure and function description

submenu

serial number

Menu Display

meaning

Select option or numerical range

1

measurement method

Test-Mode

Key testing

KEY

Measurement method selection

(Default key test)

Key testing/Automatic/Continuous

KEY/AUTO/RUN

Keytest: PressThe Test key completes one measurement.

Automatic: From empty to probe insertion and stable completion of one measurement.

Continuous: Continuously and continuously aboutMeasure every 3 seconds.

2

buzzer

Beep

open

ON

Buzzer switch selection

(default enabled)

open/Close it

ON/OFF

In the menu, pressThe "E" key enters the selected parameter modification state. If it is a numeric input type parameter, enter the number through the "+" key, “<”Press the key to move the input cursor position, press the "E" key to confirm the input, and the detector will automatically update the setting parameters and store them; If the parameter is a selection type, use a "+" or“<”Flip up and down the selection options, select the content and press the "E" key to confirm. The transmitter will automatically update the setting parameters and store them.

4. Engineer menu

In the auxiliary interface password input state, enterThe password '33' enters the engineer menu, and the structure of the engineer menu is shown in the following figure.

table 3. Structure and Function Description of Engineer Menu

menu

serial number

Menu Display

meaning

Select option or numerical range

1

language

Language

Chinese/ENGLISH

Choose language

Chinese/ENGLISH

2

Qualified method

OK-Mode

Greater than the lower limit

F>min

Qualified method selection

(Default greater than lower limit)

Greater than the lower limit/Less than upper limit, greater than lower limit/less than upper limit

F>min/MAX>F>min/MAX>F

3

Qualified upper limit

OK-MAX

N

XXX.XX

Set the upper limit of qualified touch force

(Default)80.00)

0-999.99

4

Qualified lower limit

OK-min

N

XXX.XX

Set the lower limit of qualified contact force

(Default)40.00)

0-999.99

In the menu, pressThe "E" key enters the selected parameter modification state. If it is a numeric input type parameter, enter the number through the "+" key, “<”Press the key to move the input cursor position, then press the "E" key to confirm the input. The transmitter will automatically update the setting parameters and store them; If the parameter is a selection type, use a "+" or“<”Flip up and down the selection options, select the content and press the "E" key to confirm. The transmitter will automatically update the setting parameters and store them.

5. Production calibration menu

The production calibration of instruments should be carried out by professionals with a deep understanding of instruments under the condition of calibration equipment with corresponding accuracy. At least there should be force application equipment with corresponding range, with accuracy better than0.1%The voltmeter. Without corresponding equipment and sufficient professional knowledge, improper calibration will result in the instrument not working properly. After confirming the password, you can enter the production settings state and set the corresponding instrument parameters.

In the auxiliary interface password input state, enterThe "96" password enters the production calibration menu, and the structure of the production calibration menu is shown in the following figure. The functions and parameter meanings of each menu are shown in the following table:

table 4. Structure and Function Description of Production Calibration Menu

serial number

Menu Display

meaning

Select option or numerical range

1

initialization

Enter password XX

Initialize parameters

Enter passwordAt 70 o'clock, EE is initially set as the program value

Enter password79 Save EE parameters in 101F small page

2

100% contact force value

100%Fmax=

N

XXX. XX

Set the upper limit of touch force sensing

(Default)200 cows)

Enter passwordAt 90 o'clock, EE was restored to the factory 101F value

Usually refers to the full-scale value of instruments or sensors

3

School Touch Power100%

ADJ 100%Fmax

AD=XXX

save

SAVE

School contact force channel

100% point

Press firstConfirm with E to display the sampled value, save/modify

S does not store, E stores the value.

+Or<replace withmodify

CHANGE

pressThe value can be changed after E; Press E again to save, S not to save

4

75% contact force value

75%Fmax=

N

XXX. XX

Set up touch force sensing75% value

XXX.XX

5

School Touch Power75%

ADJ 75%Fmax

AD=XXX

save

SAVE

School contact force channel

75% points

Press firstConfirm with E to display the sampled value, save/modify

S does not store, E stores the value.

+Or<replace withmodify

CHANGE

pressThe value can be changed after E; Press E again to save, S not to save

6

50% contact force value

50%Fmax=

N

XXX. XX

Set up touch force sensing50% value

XXX.XX

7

School Touch Power50%

ADJ 50%Fmax

AD=XXX

save

SAVE

School contact force channel

50% points

Press firstConfirm with E to display the sampled value, save/modify

S does not store, E stores the value.

+Or<replace withmodify

CHANGE

pressThe value can be changed after E; Press E again to save, S not to save

8

25% touch force value

25%Fmax=

N

XXX. XX

Set up touch force sensing25% value

XXX.XX

9

School Touch Power25%

ADJ 25%Fmax

AD=XXX

save

SAVE

School contact force channel

25% points

Press firstConfirm with E to display the sampled value, save/modify

S does not store, E stores the value.

+Or<replace withmodify

CHANGE

pressThe value can be changed after E; Press E again to save, S not to save

10

Zero point of school contact force

ADJ ZERO F=0

AD=XXX

save

SAVE

School contact force channel

0% point AD0

Press firstConfirm with E to display the sampled value, save/modify

S does not store, E stores the value.

+Or<replace withmodify

CHANGE

pressThe value can be changed after E; Press E again to save, S not to save

In the menu, pressThe "E" key enters the selected parameter modification state. If it is a numeric input type parameter, enter the number through the "+" key, “<”Press the key to move the input cursor position, press the "E" key to confirm the input, and the detector will automatically update the setting parameters and store them; If the parameter is a selection type, use a "+" or“<”Flip up and down the selection options, select the content and press the "E" key to confirm. The transmitter will automatically update the setting parameters and store them.