SF6+O2 system control cabinet

NegotiableUpdate on 12/19
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

The SF6+O2 system control cabinet is a central control device that monitors the concentration of sulfur hexafluoride and oxygen in the air, as well as the ambient temperature and humidity in the indoor electrical equipment workplace in real time; The equipment is equipped with a 7-inch true color touch screen to display the SF6 and O2 concentration values of each node; Sound and light alarms will be triggered when the alarm setting value is exceeded; The device has human infrared monitoring function; Real time detection data records and alarm records can be uploaded online through RS485 communication and WIFI communication functions; Widely used in the gas analysis industry, industrial process control, environmental monitoring, and power plant substations.

Product Details

SF6+O2 system control cabinetfeature

7Inch industrial true color touch display screen

Fast response time

Live voice broadcast

Equipped with sound and light alarms

Explosion proof design

Linkage windmachine/exhaust fan

auto time calibration

Having noneline/wired communication

toolpreparePIRInfrared monitoring function, supporting human body sensing, with a wide sensing rangeYu3M

Equipped with historical data recording and querying, automatic alarm event recording, fault recording, and no loss in case of power failure

High reliability, long lifespan(10Year)

Small size, compact structure, easy to install


SF6+O2 system control cabinetTechnical Specifications

display screen

7Inch true color display screen

touch method

resistive touch

resolution

800*480

alarm method

Live voice broadcastreport/audible and visual alarm

Fan starting point

SF6thickdegree1000ppmO2thickdegree19.6%vol

Fan start-up conditions

1.Manual coercion;
2.SF6Overlimit or hypoxia;
3.Timed exhaust

Relay capacity

250VAC/10A

Storage time of historical data

call the policevalue10year

driving capability

32Road detection unit

output method

1.RS485communication
2.WIFIcommunication

communication distance

1000m

Human infrared examination distance

3m

dielectric strength

1500VAC(Power supply to the earth)

Product dimensions

378*244*107mm

Product weight

TBD

design life

10year

IPProtection level

IP54(Can be customized according to actual application)

product standard

DL/T 1555-2016DL/T 639JB/T 10893

working conditions

-20-+500-90%RH(Non condensing)

test environment

0-+400-85%RH(Non condensing)

Working pressure

86kPa-106kPa

Suitable for

indoor

power supply voltage

AC220V±10%50HZ±1%

operating frequency

50HZ

rated power

<15W

Please refer to the specification sheet for specific parameters.