Welcome Customer !

Membership

Help

Shanghai Hongcen Automation Instrument Co., Ltd
Custom manufacturer

Main Products:

instrumentb2b>Products

Shanghai Hongcen Automation Instrument Co., Ltd

  • E-mail

    hongcenyibiao@163.com

  • Phone

    17316309355

  • Address

    No. 1000 Linxian Road, Tinglin Industrial Zone, Jinshan District, Shanghai

Contact Now

Pressure transmitter

NegotiableUpdate on 12/14
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

The EJA-A pressure transmitter adopts single crystal silicon resonant sensor technology and is suitable for measuring the pressure of liquids, gases, or vapors. The EJA430E converts measured pressure into a 4-20mA DC current signal output, with functions such as fast response, remote monitoring, and self diagnosis.

Product Details

  

Product description

EJA-A pressure transmitter

EJA430E/High performance pressure transmitter adopts monocrystalline silicon resonant sensor technology, suitable for measuring the pressure of liquids, gases or vapors. The EJA430E converts measured pressure into a 4-20mA DC current signal output, with functions such as fast response, remote monitoring, and self diagnosis.

EJA-A pressure transmitterThe functional features include:

Accuracy ± 0.055% (optional accuracy ± 0.04%)

Stability ± 0.1% URL/10 years

Response time of 90 milliseconds

TUV and Exida SIL2/SIL3 certification

Local parameter settings (LPS)

Provide communication protocols such as HART 5/7, HART (1-5V DC) low-power type, FF fieldbus, PROFIBUS PA, and BRAN.

  

Overview of EJA430E

Please refer to the general specification sheet under the "Data Download" tab for detailed specifications.

measurement type

main variable

gauge pressure

Reference accuracy

main variable

± 0.055% ± 0.04% (/HAC specification)

stability

main variable

± 0.1% URL/10 years

response time

main variable

90 milliseconds

turndown ratio

main variable

100:1

Blasting pressure (absolute value)

EJA430E

Liquid receiving component code S: 10000 psi
All other liquid receiving components: 6800 psi

Specification consistency

EJA-E series

±3σ

























EJA430E membrane box

Durable and sturdy construction

Durable and sturdy construction can help reduce malfunctions in your factory. Four bolt pressure holding design, DPharp digital sensor, PTFE coated 316L stainless steel flange gasket, ANSI/ISA 12.27.01 certified dual seal - all design features aim to extend the lifespan of the transmitter.
Attention: Please refer to the general specifications of each model for NACE MR0175/MR0103 standards.

Overvoltage protection

Not only does the sturdy design of the DPharp sensor itself resist the effects of overpressure, but the mechanical design inside the membrane box further provides overpressure protection, protecting the transmitter from overpressure events such as incorrect valve group operation and unexpected pressure surges, and even damage.

Independent third-party certification

The performance and reliability of the EJA-E series transmitters have been certified by international independent third-party organizations T Ü V Rheinland and EXIDA.

Functional Safety

The EJA-E series transmitters are designed in accordance with the IEC61508:2010 (Parts 1-7) and IEC61511:2004 (Parts 1-3) standards and have obtained certification. Each unit meets SIL2 safety requirements, and redundant use meets SIL3 safety requirements. By using the EJA/EJX series transmitters, one can meet production applications and safety requirements without the need for redundant configuration.

DPharp digital sensor

The DPharp digital sensor continuously outputs frequency signals even when the process pressure remains unchanged. So if the sensor malfunctions, the transmitter can detect it immediately without mistaking the sensor malfunction for unchanged process pressure.

Back Check Self Test System

The Back Check self-test system that has been acquired performs real-time reverse calculation while transmitting and converting signals from the transmitter to confirm and detect the correctness of the calculations.