1. Conductivity current test of valve type lightning arrester.
2. DC withstand voltage test and leakage current measurement of power transformers.
3. DC withstand voltage test and leakage current measurement of high-voltage cables (35-500kV and below).
4. U1mA DC reference voltage test and 0.75U1mA leakage current test for zinc oxide lightning arrester.
| specification | 60/2 | 60/3 | 60/5 | 120/2 | 120/3 | 120/5 |
| Rated voltage (kV) | 60 | 60 | 60 | 120 | 120 | 120 |
| Rated current (mA) | 2 | 3 | 5 | 2 | 3 | 5 |
| Rated power (W) | 120 | 180 | 300 | 240 | 360 | 600 |
| Whole machine weight (kg) | 9 | 10 | ||||
| Overall volume (mm)3) | 465*390*190 | 565*390*190 | ||||
| Height of pressure doubling cylinder (mm) | 440 | 535 | ||||
| Output voltage accuracy | ± (1.0% reading ± 2 words) | |||||
| Output current accuracy | ± (1.0% reading ± 2 words) | |||||
| ripple factor | ≤0.5% | |||||
| working method | Intermittent use, rated load for 30 minutes | |||||
| overload capacity | The no-load voltage can exceed the rated voltage by 10% and be used for 10 minutes | |||||
| The maximum charging current is 1.25 times the rated current | ||||||
| Power supply: AC220V ± 10% 50Hz | ||||||
| working environment | Temperature: -10-40 ℃ | |||||
| Relative humidity: not exceeding 85% at room temperature of 25 ℃ (no condensation) | ||||||
| Altitude: below 1500 meters | ||||||
| Rated voltage of lightning arrester (kV) | 10 | 35 | 66 | 110 | 220 |
| DC reference voltage kV | 28 | 90 | 135 | 168 | 314 |
| Equipment selection kV/mA | ZGF - 60 / 2 | ZGF - 120 / 2 | ZGF - 200 / 2 | ZGF - 200 / 2 | ZGF - 400 / 3 |
| Substation voltage level kV | 10 | 35 | 66 | 110 | 220 | 330 |
| Maximum test voltage kV | 47 | 105 | 135 | 192 | 305 | Greater than 400 |
| Equipment selection kV/mA | ZGF - 60 / 2 | ZGF - 120 / 2 | ZGF - 200 / 2 | ZGF - 200 / 2 | ZGF - 400 / 3 | ZGF - 800 / 10 |
| Maintenance and testing level | Level 5 | Level 4 | Level 3 | Level 2 | Level 1 |
| Maximum test voltage kV | 28 | 90 | 168 | 305 | Greater than 400 |
| Equipment selection kV/mA | ZGF - 60 / 2 | ZGF - 120 / 2 | ZGF - 200 / 2 | ZGF - 400 / 3 | ZGF - 800 / 10 |
| Rated voltage of cable Uo/U kV | 3.6 / 6 | 6 / 6 | 6 / 10 | 8.7 / 10 | 21 / 35 | 26 / 35 |
| DC test voltage kV | 17 | 30 | 40 | 47 | 105 | 130 |
| Equipment selection kV/mA | ZGF - 60 / 2 | ZGF - 60 / 2 | ZGF - 60 / 2 | ZGF - 60 / 2 | ZGF - 120 / 3 | ZGF - 200 / 5 |
| Rated voltage of cable Uo/U kV | 6 / 10 | 8.7 / 10 | 21 / 35 | 26 / 35 | 48 / 66 | 64 / 110 | 127 / 220 |
| DC test voltage kV | 26 | 37 | 63 | 78 | 144 | 192 | 305 |
| Equipment selection kV/mA | ZGF - 60 / 2 | ZGF - 60 / 2 | ZGF - 120 / 5 | ZGF - 120 / 5 | ZGF - 200 / 5 | ZGF - 200 / 10 | ZGF - 400 / 5 |
| Rated voltage of cable Uo/U kV | 48 / 66 | 64 / 110 | 127 / 220 | 190 / 330 | 290 / 500 |
| DC test voltage kV | 175 | 275 | 475 | 585 | 775 |
| Equipment selection kV/mA | ZGF - 200 / 3 | ZGF - 300 / 3 | ZGF - 500 / 5 | ZGF - 600 / 5 | ZGF - 800 / 10 |
1. Stable output voltage: High frequency voltage doubling circuit is adopted, and new PWM pulse width modulation technology and voltage current dual loop feedback technology are applied to improve power regulation and load regulation, resulting in high voltage stability and low ripple.
2. Comprehensive protection: It has complete protection functions, including zero protection, overvoltage protection, overcurrent protection, and breakdown protection. The protection circuit uses nanosecond level dedicated sensors, which act quickly and reliably, effectively ensuring personal and equipment safety.
3. 0.75U Function: An intelligent high-precision 0.75U function button is added. Pressing this button will automatically switch the voltage and current to the 0.75U state, which is beneficial for testing zinc oxide lightning arresters.
4. Zero to zero boost: The boost potentiometer uses an imported multi turn potentiometer for zero to zero boost, ensuring a smooth boost process and high adjustment accuracy.
5. Overvoltage setting: The overvoltage setting uses a digital dip switch, which is easy to operate and has high setting accuracy.
6. Integrated design: Adopting an integrated design scheme, the host and the pressure doubler are placed in one chassis. Imported high-frequency and high-voltage rectifier diodes are selected to make the voltage doubler compact in size, improve overall efficiency, and facilitate portability.
7. Reliable performance:Power frequency high-voltage generatorHigh performance imported components are selected as key components, and the outer surface of the pressure doubling cylinder is coated with special insulation materials, which have good electrical performance, strong moisture resistance, and no leakage.
8. Easy to operate:Power frequency high-voltage generatorThe layout of each functional button on the interface is reasonable, the instructions are clear, and it is easy to learn and use.