Portable comprehensive gas analyzer

NegotiableUpdate on 12/19
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin
Overview
Portable comprehensive gas analyzer is mainly used to detect and analyze SO2, H2S, CO, etc. in SF6 gas of electrical equipment such as GIS switches and SF6 circuit breakers, and quickly diagnose internal faults of electrical equipment. Different models can be selected to accurately detect and analyze the purity and micro water content of SF6 gas, fully meeting the requirements of relevant standards in the power industry.
Product Details
Portable comprehensive gas analyzerProduct Introduction

Sulfur hexafluoride (SF6) is a colorless, odorless, odorless, and non-toxic non combustible gas at room temperature and pressure, with excellent thermal stability. Its insulation performance and fire extinguishing performance are greatly superior to insulating oil. Under the same conditions, its insulation capacity is more than 2.5 times that of air and nitrogen, and its arc extinguishing capacity is 100 times that of air, making it currently an excellent insulation and arc extinguishing medium. Therefore, it is widely used in the power, electronics, and electrical industries, as well as in laser, medical, meteorological, refrigeration, firefighting, chemical, military, aerospace, non-ferrous metallurgy, physics research, and more. GIS switchgear, SF6 circuit breakers and other electrical equipment use SF6 gas as the insulation medium to achieve insulation and arc extinguishing functions.

The Gasboard-3000 series is a high-performance portable decomposition gas analyzer independently developed by Sifang Instrument. It is mainly used to detect and analyze SO2, H2S, CO, etc. in SF6 gas of electrical equipment such as GIS switches and SF6 circuit breakers, and quickly diagnose internal faults of electrical equipment. Different models can be selected to accurately detect and analyze the purity and micro water content of SF6 gas, fully meeting the requirements of relevant standards in the power industry.

Portable comprehensive gas analyzerProduct Features

Excellent performance, linear error less than 2% F.S., response time less than 60 seconds

Optimal absorption peak and interference compensation algorithm with minimal cross interference

The light source uses imported xenon lamps, which have high stability

Portable chassis design for easy integration and maintenance

Powered by lithium-ion batteries, with a battery life of over 4 hours and an RS-232 communication interface output, convenient for on-site operations by customers


Basic Principles

The Gasboard-3000 series gas analyzer is a composite optical measurement solution based on UV-DOAS, TDLAS, and micro flow NDIR technologies. The product light source adopts imported xenon lamps, which use the differential absorption characteristic intensity generated by each molecule in different wavelength bands when light is transmitted in the gas to deduce the gas type and concentration. Using different algorithms, the gas chamber returns multiple times with a long optical path, which has the characteristics of high sensitivity, strong signal absorption, long service life, and good stability. Can accurately measure SF6Trace amounts of SO in gases2、H2S. CO gas concentration, with a measurement range of less than 100ppm.


Technical Specifications

Analyzer series Integrated gas analyzer
model Gasboard-3000F
Main functions SO2, H2S, CO gas concentration

SF6 gas purity

SF6 gas micro water content

measurement range SO2:0~100ppm

H2S:0~100ppm

CO:0~1000ppm

SF6: 0~100%

Dew point temperature: -80 ℃~20 ℃

detection accuracy Decomposition products ≤± 2% F.S

Dew point temperature ≤ 0.5 ℃

resolution SO2/H2S:0.1ppm

CO:1ppm

SF6:0.01%

Dew point temperature: 0.1 ℃

warm-up time 800s
Zero/End Drift ±2%F.S./4h
working conditions 5℃~40℃
Pump valve requirements Pump valve control zeroing
contact method RS232