8. protection function
8.1 Differential quick break protection
Differential speed determination value range |
4.0Ie~14.0Ie |
Current setting error |
≤Current constant value×2.5%or 0.02Ie middleThe larger one |
Action time of differential quick break protection |
≤ 25ms(1.5×Differential speed determination value) |
8.2 Ratio differential protection
Range of starting values for differential current |
0.05Ie~1.5Ie |
Current setting error |
≤ Current constant value×2.5%or 0.02Ie Medium to large |
Range of ratio differential braking coefficient |
0.3~0.75 |
Range of second harmonic braking coefficient |
0.05~0.35 |
Action time of ratio differential protection |
≤35ms(2×Differential current starting value) No harmonic blocking |
8.3 overcurrent protection
Current setting range |
0.05×In ~ 30×In |
Current setting error |
≤Current constant value×±2.5%or ±0.01In Medium to large |
Delay setting range |
0.00s ~ 100.00s |
Delay setting error |
≤Delay fixed value×1% + 35ms(1.5X current settingValue) |
8.4 Overcurrent inverse time limit protection
Starting current(Ip)Fixed value range |
0.05×In ~ 4.0×In |
Time multiplier setting range |
0.05 ~ 100 |
Starting current setting |
1.0×Setting |
return coefficient |
0.95 |
Current setting error |
< 2.5%or 0.01×In Medium to large |
Trip time error(1.2<I/Ip<30) |
Max(5%Calculated value) and Max(2.5%Caused by current error The sum of calculation time errors,or 35ms |
8.5 Negative sequence overcurrent protection
Current setting range |
0.05×In ~ 4.0×In |
Starting current setting |
1.0×Setting |
return coefficient |
0.95 |
Current setting error |
< 2.5%or 0.01In Medium to large |
Time setting range |
0 100s |
Time setting error |
< Time fixed value×1%+50ms |
8.6 Nanjing Nanrui Jibao PCS9621 microcomputer comprehensive protection
Zero sequence overcurrent protection
Current setting range |
0.05 ~ 30A(External) |
Current setting error |
≤Current constant value×±2.5%or ±0.02A Mid term comparisonThe big one |
Delay setting range |
0.00s ~ 100.00s |
Delay setting error |
≤Delay fixed value×1% + 35ms |
8.7 Overload protection
Current setting range |
0.05×In ~ 30×In |
Current setting error |
≤Current constant value×±2.5%or ±0.01In Medium to large |
Delay setting range |
0.00s ~ 100.00s |
Delay setting error |
≤Delay fixed value×1% + 35ms |
8.8 Overcurrent acceleration protection
Current setting range |
0.05×In ~ 30×In |
Current setting error |
≤Current constant value×±2.5%or ±0.01In Medium to large |
Delay setting range |
0.00s ~ 100.00s |
Delay setting error |
≤Delay fixed value×1% + 35ms |
8.9 Zero sequence acceleration protection
Current setting range |
0.05 ~ 30A(External) |
Current setting error |
≤Current constant value×±2.5%or ±0.02A Mid term comparisonThe big one |
Delay setting range |
0.00s ~ 100.00s |
Delay setting error |
≤Delay fixed value×1% + 35ms |
8.10 voltage protection
Zero sequence overvoltage setting range |
2 ~200V |
||
Low voltage setting range |
2 ~100V |
||
Overvoltage setting range |
2 ~ 160V |
||
Voltage setting error |
< 2.5%or 0.10V Medium to large |
||
Time setting range |
0.1~100s |
||
Action time error |
≤Delay fixed value×1% + 35ms |
||
8.11 overheat protection
Range of reference current setting |
0.05×In ~ 3×In |
Current setting error |
≤Current constant value×±2.5%or ±0.01In Medium to large |
Time constant range |
10s ~ 6000s |
Range of heat dissipation time constant |
0.1s ~ 30000s |
Delay setting error |
≤Delay fixed value×1% + 35ms |
Thermal overload coefficient |
1~3 |
8.12
Non electricity protection
Protection trip long delay |
0~4000s |
Protection trip short delay |
0~100s |
Delay setting error |
≤Delay fixed value×1% + 35ms |
8.13 Low frequency load shedding protection
Frequency setting range |
45~50Hz |
Frequency setting error |
±0.01Hz |
DFDT Closed lock value range |
0.3~20Hz/s |
Delay setting range |
0.00s ~ 100.00s |
Delay setting error |
≤Delay fixed value×1% + 35ms |
8.14
recloser
Delay setting range |
0.1s ~ 10.0s |
Delay setting error |
≤Delay fixed value×1% + 35ms |
9. management function
9.1 Fault recording and event recording
|
Fault recording and fault event reporting |
Before starting the entire set of startup records 2 One cycle, after startup 6 Waveform of one cycle |
Before starting the protection action record 2 One cycle, after startup 6 aZhou Bo, before the action 2 One cycle After the action 6 A cycle and disturbances in the middle 16 A waveform of one cycle. | |
Recyclable recording 64 Secondary protection action report64 Secondary fault recording. | |
正常波形 |
recordable 5 A waveform of one cycle for recording or polarity verification. |
abnormal alarm |
Recyclable recording 1024 Abnormal alarm and device self-test report. |
Switching displacement |
Recyclable recording 1024 Secondary switch displacement report. Switching quantity change packageIncluding various inputs and outputs Status changes, etc. |