Welcome Customer !

Membership

Help

Hangzhou Hangrui Electric Power Automation Co., Ltd
Custom manufacturer

Main Products:

instrumentb2b>Products
Product Categories

Hangzhou Hangrui Electric Power Automation Co., Ltd

  • E-mail

  • Phone

  • Address

    Building 2, No. 64 Tiancheng Road, Jianggan District, Hangzhou City, Zhejiang Province

Contact Now

Nanjing Nanrui Jibao PCS9621 microcomputer comprehensive protection

NegotiableUpdate on 05/14
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

Nanjing Nanrui Jibao PCS9621 microcomputer comprehensive protection $r $n operation alarm: $r $nl accident total signal $r $nl CT disconnection alarm $r $nl bus PT disconnection alarm $r $nl control circuit disconnection alarm $r $nl TWJ abnormal alarm $r $nl overload alarm $r $n $r $nl zero sequence section III alarm $r $nl grounding alarm $r $nl over temperature alarm $r $nl spring energy storage alarm $r $nl frequency abnormal alarm $r $nl light gas alarm $r $nl non electricity 2 alarm

Product Details

Nanjing Nanrui Jibao PCS9621 microcomputer comprehensive protection

8. protection function

8.1 Differential quick break protection

Differential speed determination value range

4.0Ie~14.0Ie

Current setting error

Current constant value×2.5%or 0.02Ie middleThe larger one

Action time of differential quick break protection

≤ 25ms(1.5×Differential speed determination value)

8.2 Ratio differential protection

Range of starting values for differential current

0.05Ie~1.5Ie

Current setting error

Current constant value×2.5%or 0.02Ie Medium to large

Range of ratio differential braking coefficient

0.3~0.75

Range of second harmonic braking coefficient

0.05~0.35

Action time of ratio differential protection

≤35ms(2×Differential current starting value) No harmonic blocking

8.3 overcurrent protection

Current setting range

0.05×In ~ 30×In

Current setting error

Current constant value×±2.5%or ±0.01In Medium to large

Delay setting range

0.00s ~ 100.00s

Delay setting error

Delay fixed value×1% + 35ms1.5X current settingValue)

8.4 Overcurrent inverse time limit protection

Starting current(Ip)Fixed value range

0.05×In ~ 4.0×In

Time multiplier setting range

0.05 ~ 100

Starting current setting

1.0×Setting

return coefficient

0.95

Current setting error

< 2.5%or 0.01×In Medium to large

Trip time error(1.2<I/Ip<30

Max5%Calculated value) and Max2.5%Caused by current error The sum of calculation time errors,or 35ms

8.5 Negative sequence overcurrent protection

Current setting range

0.05×In ~ 4.0×In

Starting current setting

1.0×Setting


return coefficient

0.95

Current setting error

< 2.5%or 0.01In Medium to large

Time setting range

0 100s

Time setting error

< Time fixed value×1%50ms

8.6 Nanjing Nanrui Jibao PCS9621 microcomputer comprehensive protection

Zero sequence overcurrent protection

Current setting range

0.05 ~ 30A(External)

Current setting error

Current constant value×±2.5%or ±0.02A Mid term comparisonThe big one

Delay setting range

0.00s ~ 100.00s

Delay setting error

Delay fixed value×1% + 35ms

8.7 Overload protection

Current setting range

0.05×In ~ 30×In

Current setting error

Current constant value×±2.5%or ±0.01In Medium to large

Delay setting range

0.00s ~ 100.00s

Delay setting error

Delay fixed value×1% + 35ms

8.8 Overcurrent acceleration protection

Current setting range

0.05×In ~ 30×In

Current setting error

Current constant value×±2.5%or ±0.01In Medium to large

Delay setting range

0.00s ~ 100.00s

Delay setting error

Delay fixed value×1% + 35ms

8.9 Zero sequence acceleration protection

Current setting range

0.05 ~ 30A(External)

Current setting error

Current constant value×±2.5%or ±0.02A Mid term comparisonThe big one

Delay setting range

0.00s ~ 100.00s

Delay setting error

Delay fixed value×1% + 35ms

8.10 voltage protection

Zero sequence overvoltage setting range

2 200V

Low voltage setting range

2 100V

Overvoltage setting range

2 160V

Voltage setting error

< 2.5%or 0.10V Medium to large

Time setting range

0.1100s


Action time error

Delay fixed value×1% + 35ms


8.11 overheat protection

Range of reference current setting

0.05×In ~ 3×In

Current setting error

Current constant value×±2.5%or ±0.01In Medium to large

Time constant range

10s ~ 6000s

Range of heat dissipation time constant

0.1s ~ 30000s

Delay setting error

Delay fixed value×1% + 35ms

Thermal overload coefficient

1~3


8.12


Non electricity protection


Protection trip long delay

0~4000s

Protection trip short delay

0~100s

Delay setting error

Delay fixed value×1% + 35ms

8.13 Low frequency load shedding protection

Frequency setting range

45~50Hz

Frequency setting error

±0.01Hz

DFDT Closed lock value range

0.320Hz/s

Delay setting range

0.00s ~ 100.00s

Delay setting error

Delay fixed value×1% + 35ms


8.14


recloser


Delay setting range

0.1s ~ 10.0s

Delay setting error

Delay fixed value×1% + 35ms

9. management function

9.1 Fault recording and event recording

Fault recording and fault event reporting

Before starting the entire set of startup records 2 One cycle, after startup 6 Waveform of one cycle

Before starting the protection action record 2 One cycle, after startup 6 aZhou Bo, before the action 2 One cycle After the action 6 A cycle and disturbances in the middle 16 A waveform of one cycle.

Recyclable recording 64 Secondary protection action report64 Secondary fault recording.

正常波形

recordable 5 A waveform of one cycle for recording or polarity verification.

abnormal alarm

Recyclable recording 1024 Abnormal alarm and device self-test report.

Switching displacement

Recyclable recording 1024 Secondary switch displacement report. Switching quantity change packageIncluding various inputs and outputs Status changes, etc.