Welcome Customer !

Membership

Help

Hangzhou Hangrui Electric Power Automation Co., Ltd
Custom manufacturer

Main Products:

instrumentb2b>Products
Product Categories

Hangzhou Hangrui Electric Power Automation Co., Ltd

  • E-mail

  • Phone

  • Address

    Building 2, No. 64 Tiancheng Road, Jianggan District, Hangzhou City, Zhejiang Province

Contact Now

Nanjing Nanrui Jibao PCS9621 Protection Device

NegotiableUpdate on 05/14
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

Nanjing Nanrui Jibao PCS9621 protection device protection configuration: $r $nl three-stage composite voltage blocking overcurrent protection $r $nl high-voltage side positive sequence inverse time limit protection $r $nl two-stage timed negative sequence overcurrent protection $r $nl high-voltage side grounding protection (three-stage timed zero sequence overcurrent protection, zero sequence $r $n protection configuration: $r $nl three-stage composite voltage blocking overcurrent protection $r $nl high-voltage side positive sequence inverse time limit protection $r $nl two-stage timed negative sequence overcurrent protection $r $nl high-voltage side grounding protection (three-stage timed zero sequence overcurrent protection, zero sequence overvoltage protection, supporting network small current grounding) Line selection)

Product Details

Nanjing Nanrui Jibao PCS9621 Protection Device

mechanical structure

mechanical dimensions

See 10.1 section

cutout size

See 10.1 Festival,M6 screw

color

silver gray

Device weight

about 7kg

pollution level

secondary

Protection level

front panel IP40Side of the box IP50 Rear panel IP30 GB 4208-2008


5.1 EIA-485interface

Baud rate

4.8kbit/s The9.6kbit/s The19.2kbit/s The38.4kbit/s The57.6kbit/s The115.2kbit/s

communication protocol

DL/T 667-1999idt IEC 60870-5-103:1997

maximum load

32


transmission distance

<500m

Wiring form

shielded twisted pair

5.2 Ethernet interface

interface form

RJ-45

transmission rate

100Mbits/s adaptive

Transmission standards

10Base-T/100Base-TX

transmission distance

<100m

communication protocol

IEC 60870-5-103:1997 or IEC 61850

Wiring form

Five types of shielded network cables

5.3 Fiber optic interface (station control layer)

feature

Glass fiber optic

terminal

SC ST

Fiber optic cable type

multimodal

Typical transmission distance

<2km

Light wave length

1310nm

Minimum transmission power

Min. –20.0dBm

reception sensitivity

Min. –30.0dBm

System reserve

Min +3.0 dB

5.4 Printing interface

Number of ports

1

Baud rate

4.8kbit/s The9.6kbit/s The19.2kbit/s The38.4kbit/s The57.6kbit/s The115.2kbit/s

printer model

Serial port needle printer

interface form

RS-232

5.5 Time synchronization interface

transmission distance

<500m

Maximum load capacity

32

Time synchronization standard

Second pulse,Split pulse, IRIG-B

interface form

RS-485

Nanjing Nanrui Jibao PCS9621 Protection Device

8. protection function

8.1 Differential quick break protection

Differential speed determination value range

4.0Ie~14.0Ie

Current setting error

Current constant value×2.5%or 0.02Ie middleThe larger one

Action time of differential quick break protection

≤ 25ms(1.5×Differential speed determination value)

8.2 Ratio differential protection

Range of starting values for differential current

0.05Ie~1.5Ie

Current setting error

Current constant value×2.5%or 0.02Ie Medium to large

Range of ratio differential braking coefficient

0.3~0.75

Range of second harmonic braking coefficient

0.05~0.35

Action time of ratio differential protection

≤35ms(2×Differential current starting value) No harmonic blocking

8.3 overcurrent protection

Current setting range

0.05×In ~ 30×In

Current setting error

Current constant value×±2.5%or ±0.01In Medium to large

Delay setting range

0.00s ~ 100.00s

Delay setting error

Delay fixed value×1% + 35ms1.5X current settingValue)

8.4 Overcurrent inverse time limit protection

Starting current(Ip)Fixed value range

0.05×In ~ 4.0×In

Time multiplier setting range

0.05 ~ 100

Starting current setting

1.0×Setting

return coefficient

0.95

Current setting error

< 2.5%or 0.01×In Medium to large

Trip time error(1.2<I/Ip<30