Japanese M7103 power measurement module

NegotiableUpdate on 05/20
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

Suitable for high-precision and compact photovoltaic inverter detection systems. $r $n ∝ Ensure accuracy of DC1500V; $r $n ∝ 19 inch rack with 4U size space can accommodate up to 12 channels; $r $n ∝ can be expanded from 12 channels to a maximum of 10 sets of 120 channels; Stable efficiency measurement is achieved through multi synchronous source collaborative technology.

Product Details

Product Specifications

Compatible Models

Data acquisition instrument LR8101: standard model

Data acquisition instrument LR8102: high-performance model

Temperature and humidity range for use

0 ℃~40 ℃, below 80% RH (no condensation)

Measurement line

Single phase 2-wire (1P2W)

Single phase 3-wire (1P3W)

Three phase three wire (3P3W2M, 3V3A, 3P3W3M)

Three phase 4-wire (3P4W)

Number of power channels

3 power channels

input terminal

Voltage: Plug in terminal (safety terminal)

Current: Special connector (ME15W)

input method

Voltage: Insulation input, resistance voltage division method

Current: Insulated input through current sensor (voltage output)

voltage range

6 V, 15 V, 30 V, 60 V, 150 V, 300 V, 600 V, 1500 V

current range

0.04A~20kA (depending on the current sensor used)

Peak factor

3 (rated relative voltage and current range), but the 1500 V range is 1.35

Input resistance, input capacitance

Voltage input section: 3 M Ω± 30 k Ω, 1.5 pF typical

Current sensor input: 1 M Ω± 50 k Ω

Maximum input voltage

Voltage input section: AC 1000 V, DC 2000 V

Current sensor input section: 8 V, ± 12 V peak

Maximum rated voltage to ground

AC/DC 1000 V CATIII expected transition overvoltage 8000 V

AC 1000 V/DC 1500 V CATII Expected Transition Overvoltage 8000 V

measurement method

Voltage current synchronous digital sampling and zero crossing synchronous calculation method

sampling rate

500 kHz / 16 bit

frequency bandwidth

DC, 0.1 Hz ~ 100 kHz

Effective measurement range

1% of range~110% of range

LPF (Low Pass Filter)

Choose from OFF/500 Hz/5 kHz

measurement items

Voltage (U), current (I), active power (P), apparent power (S), reactive power (Q), power factor (λ), phase angle (φ), voltage frequency (fU), current frequency (fI), voltage ripple rate (Urf), current ripple rate (Irf), current accumulation (Ih), power accumulation (WP), voltage peak value (Upk), current peak value (Ipk)

Other measurements

Frequency, accumulation, harmonics (IEC mode, wideband mode)

function

AUTO range function, calculation function, synchronous source collaboration function

Volume and weight

About 65W x 170H x 255D mm (excluding protrusions), about 1.5 kg

Attachment