- Phone
-
Address
Baoying Liubao Industrial Zone, Yangzhou City
Yangzhou Zhili Electric Technology Co., Ltd
Baoying Liubao Industrial Zone, Yangzhou City
This catalog is carefully selected by Yangzhou Zhili Electric Technology Co., Ltd. for your series resonance withstand voltage test device products. There are many types of them, and different applications may have slight differences. Our company provides you with * solutions. Zhili Company adheres to the sales philosophy of "customer is God, maximize customer satisfaction" and actively provides pre-sales, in sales, and after-sales services. Zhili products implement three guarantees and lifelong maintenance. Choosing Zhili, a professional manufacturer, allows users to experience that choosing is reassuring.
ZLXZB seriesFrequency modulation resonance withstand voltage test deviceApplied in industries such as power, metallurgy, petroleum, and chemical engineering, it is suitable for the handover and preventive testing of high-capacity capacitive samples, such as generators, power transformers, and high-voltage cross-linked cables. The TPXZB-210/60 cable AC withstand voltage test equipment can meet the AC withstand voltage test of 35kV cross-linked cables with a length of 1km. Can meet the AC withstand voltage test of 10kV cross-linked cable with a length of 2km. Can meet the AC withstand voltage test of 10kV voltage level power transformers.

ZLXZB seriesFrequency modulation resonance withstand voltage test deviceTechnical Specifications:
Environmental temperature: -10~45 ℃
Environmental humidity: ≤ 90%
Altitude: ≤ 2000M
Power input: 220V ± 10% single-phase 50Hz output 0-2220V (≤ 10KW)
380V ± 10% three-phase 50Hz output 0-400V
Rated test capacity: 0-8000KVA (optional)
Resonant voltage: 0-1000KV (optional)
Frequency adjustment range: 0.1-300Hz
System measurement accuracy: Level 0.5
Frequency regulation division rate: 0.01Hz
Instability: ≤ 0.05%
Output waveform: sine wave
Waveform distortion rate: ≤ 0.5%
Noise: ≤ 60dB
Reactor Q value: 30-200 (optional)
ZLXZB series FM resonant working environment:
1. Environmental temperature: -150C -400C;
2. Relative humidity: ≤ 90% RH;
3. Altitude: ≤ 1000 meters;
Subject and Test Requirements
1. 64/110kV/300mm2 cable, length 0.2km, capacitance ≤ 0.03uF, test frequency 30-300Hz, test voltage 128kV.
2. 26/35kV/300mm2 cable, length 1.2km, capacitance ≤ 0.228uF, test frequency 30-300Hz, test voltage 52kV.
3. 8.7/10KV/300mm2 cable, length 4km, capacitance ≤ 1.2uF, test frequency 30-300Hz, test voltage 22kV.
4. 110kV substation GIS equipment, 35kV transformer, distribution equipment AC withstand voltage, test frequency 30-300Hz, test voltage 184kV.