Overview

The ARCM200L-MU series fire engineering electrical monitoring unit (hereinafter referred to as the electrical unit) is designed for TT and TN systems below 0.4kV. It monitors and manages fire hazard parameters such as residual current, wire temperature, overcurrent, and overvoltage in the distribution circuit to prevent electrical fires and achieve real-time monitoring of various power parameters, providing accurate data for energy consumption management.

Product Details

Ankrui, Bao Jingjun, Zhao Mengling

Launched by AnkeruiARCM200L-MU seriesFire engineering electrical monitoring unitBy adopting microcontroller technology and integrating digitization and intelligence, it is your responsibility to carry outElectrical fire prevention monitoringWithEstimation of system insulation agingThe capable assistant.

⚡ Core advantage: Multi dimensional monitoring, precise warning

Unlike single function monitoring devices, ARCM200L-MUFire engineering electrical monitoring unitRealized three-dimensional protection for distribution circuits:
  • parameter monitoring: Support real-time monitoring3 three-phase voltages, 1 three-phase current, as well as basic parameters such as power and electrical energy. At the same time, focus on monitoring fire risks4 temperature channelsAndresidual current.

  • Multiple alarm mechanism: PossessOvervoltage, undervoltage, overload, overcurrent, overtemperature, leakage currentWaiting for multiple alarm functions. The alarm threshold is flexible and adjustable (leakage 300~1000mA, temperature 45~140 ℃), and the action delay time is continuously adjustable from 0.1~60S, meeting the response requirements of different scenarios.

  • Intuitive visual interface: Equipped withColor LCD display screenTransform complex power data into clear visual information, making the operating status clear at a glance.

🛠️ Intelligent Management: Linkage Control and Data Traceability

In addition to monitoring, ARCM200L-MU also has * management and control capabilities:
  • Automatic control output: Built in2-channel relay outputWhen an abnormal alarm is detected in the circuit, the control output relay is closed, which can be linked to cut off the faulty circuit or start the fire-fighting equipment; Automatically released after the alarm is eliminated, effectively preventing the accident from escalating.

  • Complete data recordingThe device has event recording and storage function, which can store20 event records, 20 fault recordsWait. These precise data provide a reliable basis for post accident analysis and tracing.

  • Hierarchical permission guaranteeSupport setting user permissions, with different levels of operators having different operational permissions to ensure the security of system settings and prevent risks caused by misoperation.

  • 消防工程电气监控单元