- Phone
-
Address
No. 5, ASEAN Road, Nanzha Town, Jiangyin City, Jiangsu Province
Jiangsu Ankerui Electric Appliance Manufacturing Co., Ltd
No. 5, ASEAN Road, Nanzha Town, Jiangyin City, Jiangsu Province
Ankrui, Bao Jingjun, Zhao Mengling
Building electrical fire monitoring unitIt is designed for TT and TN systems below 0.4kV, and monitors and manages fire hazard parameters such as residual current, wire temperature, overcurrent, and overvoltage in the distribution circuit to prevent electrical fires. It also achieves real-time monitoring of various power parameters, providing accurate data for energy consumption management.
Automatic control output: Built in2-channel relay outputWhen an abnormal alarm is detected in the circuit, the control output relay is closed, which can be linked to cut off the faulty circuit or start the fire-fighting equipment; Automatically released after the alarm is eliminated, effectively preventing the accident from escalating.
Complete data recordingThe device has event recording and storage function, which can store20 event records, 20 fault recordsWait. These precise data provide a reliable basis for post accident analysis and tracing.
Hierarchical permission guaranteeSupport setting user permissions, with different levels of operators having different operational permissions to ensure the security of system settings and prevent risks caused by misoperation.
parameter monitoring: Support real-time monitoring3 three-phase voltages, 1 three-phase current, as well as basic parameters such as power and electrical energy. At the same time, focus on monitoring fire risks4 temperature channelsAndresidual current.
Multiple alarm mechanism: PossessOvervoltage, undervoltage, overload, overcurrent, overtemperature, leakage currentWaiting for multiple alarm functions. The alarm threshold is flexible and adjustable (leakage 300~1000mA, temperature 45~140 ℃), and the action delay time is continuously adjustable from 0.1~60S, meeting the response requirements of different scenarios.
Intuitive visual interface: Equipped withColor LCD display screenTransform complex power data into clear visual information, making the operating status clear at a glance.