ARCM200L-MU seriesElectrical comprehensive monitoring unit(hereinafter referred to as the electrical unit) is designed for TT and TN systems below 0.4kV. It monitors and manages fire hazard parameters such as residual current, wire temperature, overcurrent, and overvoltage in the distribution circuit to prevent electrical fires. It also achieves real-time monitoring of multiple power parameters, providing accurate data for energy consumption management.
parameter monitoring: Support real-time monitoring3 three-phase voltages, 1 three-phase current, as well as basic parameters such as power and electrical energy. At the same time, focus on monitoring fire risks4 temperature channelsAndresidual current.
Multiple alarm mechanism: PossessOvervoltage, undervoltage, overload, overcurrent, overtemperature, leakage currentWaiting for multiple alarm functions. The alarm threshold is flexible and adjustable (leakage 300~1000mA, temperature 45~140 ℃), and the action delay time is continuously adjustable from 0.1~60S, meeting the response requirements of different scenarios.
Intuitive visual interface: Equipped withColor LCD display screenTransform complex power data into clear visual information, making the operating status clear at a glance.