ETCR2000 clamp type grounding resistance meterProduct Introduction
ETCR2000 clamp type grounding resistance meterThis is a major breakthrough in traditional grounding resistance measurement technology, widely used in the measurement of grounding resistance in power, telecommunications, meteorology, oil fields, buildings, and industrial electrical equipment.
When measuring a grounded system with a circuit, there is no need to disconnect the grounding lead or auxiliary electrodes, which is safe, fast, and easy to use.
It can measure grounding faults that cannot be measured by traditional methods and can be applied to situations where traditional methods cannot measure them, because this instrument measures the comprehensive value of grounding body resistance and grounding lead resistance.
There are two types of jaws: long jaws and round jaws. Long jaws are particularly suitable for situations where flat steel is grounded.
In addition, it can also measure the leakage current and neutral line current of the grounding system.
Other name
Single jaw grounding resistance tester, clamp type grounding resistance tester, clamp type grounding resistance meter, clamp type grounding resistance meter, clamp type grounding resistance meter, clamp type grounding resistance meter, grounding resistance, grounding surface, grounding resistance meter, grounding resistance meter, grounding resistance measuring instrument, clamp type digital grounding resistance tester, clamp type grounding resistance tester
Product features
1. The ETCR2000 clamp type grounding resistance tester is suitable for grounding leads of various shapes (round steel, flat steel, and angle steel)
2. Non contact measurement of grounding resistance, safe and fast
3. No need to use auxiliary grounding rods, no need to interrupt the grounding of the tested equipment
4. Equipped with dual protection insulation
5. Strong resistance to dryness and high measurement accuracy
6. Using No. 5 alkaline battery is convenient for users
Technical Specifications:
1. Power supply: 6VDC (4 No. 5 alkaline dry batteries)
2. Working temperature: -10 ℃~55 ℃
3. Relative humidity: 10% to 90%
4. LCD display: 4-digit LCD digital display, length x width: 47 x 28.5mm2
5. Jaw opening size: long jaw 28mm; round jaw 32mm
6. Clamp quality (including battery): Long clamp 1320g; Round clamp 1120g
7. Clamp size: Long clamp: 293mm long, 90mm wide, 66mm thick
Round jaw: 260mm long, 90mm wide, 66mm thick
8. Explosion proof mark for explosion-proof products: Exia II BT3
9. Protection level: Double insulation
10. Structural features: Clamping method
11. Range shifting: automatic
12. External magnetic field: < 40A/m
13. External electric field: < 1V/m
14. Single measurement time: 1 second
15. Resistance measurement frequency: > 1KHz
Resistance measurement with the highest resolution: 0.001 Ω
Resistance measurement range: 0.01~1000 Ω
*Current measurement range: 0.00~30.0A
*Tested current frequency: 45-65Hz
*Can store measurement data: 50 sets
*Range of critical value setting for resistance alarm: 1~199 Ω
*Current alarm critical value setting range: 1-499mA
Precautions for use:
A. During the power on self-test, the instrument should be in a relaxed and natural state, and fingers should not touch the clamp handle when holding the instrument with one hand. This is important for ensuring measurement accuracy.
B. When the measured resistance is high (e.g. greater than 100 ohms), to ensure measurement accuracy, before pressing the POWER button (i.e. before the instrument is powered on), press the clamp handle to open and close the clamp 2-3 times, and then start the instrument. This is important for ensuring measurement accuracy of resistors greater than 100 ohms.
C. Always keep the contact surface of the jaws clean. The anti pollution ability of this instrument is already very strong, but excessive pollution can still reduce the measurement accuracy of the instrument. Especially the measurement accuracy of resistors above 100 ohms.
D. The anti drying ability of this instrument is already very strong. There is sufficient resistance to dryness for the current on the tower grounding wire. However, the low-voltage transformer connected to the zero system still needs to undergo power outage testing due to its large unbalanced current.
E. Please remove the battery from the battery compartment when not using this instrument for a long time.