Anti floating buried box pump integrated constant pressure pump station $r $n Integrated prefabricated pump station generally adopts fully underground installation, which has the characteristics of small footprint and short construction period. It has been used in new construction, expansion and renovation projects of water supply and drainage and waterlogging prevention, and has advantages. In special circumstances, semi underground installation can also be used, and the wellbore structure and materials need to be specially designed.

Product Details

Anti floating buried box pump integrated constant pressure pump station


Compliant with GB50794-2014 Fire Protection Code: The fire pump motor of this product is installed dry and meets the technical specifications for fire pump motors in the "Technical Specification for Fire Water Supply and Hydrant Systems" implemented since October 1, 2014; ensuring fire safety acceptance.

The components of the integrated anti floating buried box pump are as follows: The manufacturer will popularize the relevant knowledge of the integrated buried box pump for you:

1. The fire pump station is mainly composed of a fire water pool, a fire pump room, a fire booster water supply equipment system, and a sewage system.

2. Structural form: All adopt steel structural form.

3. The installation method is a combination of bolt assembly and welding.

4. Material: hot-dip galvanized or stainless steel or composite steel plate or galvanized steel plate and 304 stainless steel composite plate.

5. Internal structure: Full hall scaffolding structure or portal steel structure; Hot dip galvanized steel pipe;

6. Pump station bearing capacity: 100-450kn/m2

7. The service life of the fire pump station is over 30 years.

8. Anti leakage and seepage prevention: using EPDM rubber sealing strips.

9. The diameter of the vent pipe is DN100 and it is led to the collection pit.

10. The ventilation system uses a 24-hour non powered ventilator.

11. The control cabinet has the functions of automatic start, manual start, remote control start, mechanical start, high and low water level alarm, automatic low-frequency inspection and manual power frequency inspection, fault memory export and transmission flow detection, remote monitoring and communication.

12. The inspection cycle for the water pumps in the fire pump station is 7 days, with each pump being inspected for 2 minutes each time.

13. What form of fire pump does our company use? Answer: According to the new fire protection standard GB50974-2014 issued on October 1, 2014; Dry motor long shaft well pump. 14. How is the depth of soil cover for anti floating underground pumping stations determined? Answer: The thickness of the soil covering the top of the pool is determined to be equal to the thickness of the frozen soil layer+300mm. If the thickness of the soil covering cannot meet the thickness of the anti floating soil covering, it shall be determined based on the calculated thickness of the anti floating soil covering.

15. Where is the low effective water level of the water tank in the "anti floating buried box pump integrated pumping station" calculated from? What measures does our company take to meet the low effective water level? The anti floating pressurized buried box pump integrated water supply equipment has replaced the standard product of concrete fire water tanks, saving more than 40% of investment. Suitable for various fire water supply systems such as fire hydrant systems and sprinkler systems with fire pressure boosting design requirements in high-rise buildings and enterprises. Product principle: This buried fire box pump integrated pump station adopts variable frequency constant pressure water supply. Compared with the traditional method of achieving constant pressure water supply for fire protection through regulating valves, the effect is more obvious (can be calculated based on detailed conditions)