Example of filling in model and parameters:
(1)N3-WRAD-3-555A4BY
0.5 Three phase three wire active power/reactive powercurrentTransmitter (cross phase method)
Input nominal current:5A; Input nominal voltage:100V;
Standard output power④(active power/reactive power):866W/866Var
Input signal frequency:50±5Hz;
Output range:4~20mACorresponding to0~5A
4~12~20mA;
correspond respectively-866~0~866W /-866~0~866Var
Auxiliary power supply:AC220VWe need to measure the reverse power.
(2)S3(T)-WRAD-3T-555A4BY
0.2 Three phase three wire active power/Reactive power transmitter (phase-shifting method)
Input nominal current:5A; Input nominal voltage:100V;
Standard output power④(active power/reactive power):866W/866Var
Input signal frequency:50±5Hz;
Output range:4~20mACorresponding to0~5A
4~12~20mA;
correspond respectively-866~0~866W /-866~0~866Var
Auxiliary power supply:AC220VWe need to measure the reverse power.
Note: ① System: marked with T, measured using phase-shifting method; No T annotation, measured using the cross phase method.
② The measurement of current in the combination transmitter is separate, and users can customize it according to their system requirementsConnect any current of phase A, B, or C arbitrarily.
③ The value within the output range () is the calibrated value for forward and reverse power output. toMeasurement of reactive power: When the output is negative, it indicates that the capacitive impedance of the system is high;When the output is positive, it indicates that the inductive impedance of the system is high.
④ The calibration of system power can be found in the previous active power annotation: item ②.
⑤ If the user requires other special calibrations, please specify the parameter values in the contract