Abnormal frequency dielectric loss tester

NegotiableUpdate on 05/06
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

The inter frequency dielectric loss tester is suitable for measuring the dielectric loss of transformers, mutual inductors, bushings, capacitors, lightning arresters and other equipment in the power industry. Reference standards: DL/T 962-2005, DL/T 474.3-2018. Note: For product purchase, technical maintenance and other services, please feel free to call!

Product Details

Dielectric loss measurement is a fundamental method in insulation testing, which can effectively detect the overall moisture degradation and deterioration of electrical equipment insulation, as well as local defects. Widely used in electrical manufacturing, electrical equipment installation, handover, and preventive testing. The measurement of dielectric loss of transformers, mutual inductors, reactors, capacitors, bushings, lightning arresters, etc. is a fundamental method for measuring their insulation performance.

Abnormal frequency dielectric loss testerBreaking through the traditional bridge measurement method, adopting variable frequency power supply technology, and utilizing single-chip microcontrollers and modern electronic technology for automatic frequency conversion, analog-to-digital conversion, and data operation; Strong resistance, fast testing speed, high accuracy, fully automated digitization, and easy operation; The power supply adopts a high-power switching power supply, which outputs pure sine waves at 45Hz and 55Hz, automatically applies voltage, and can provide a voltage of 10 kV; Automatically filter out 50Hz interference, suitable for on-site testing in substations and other areas with high electromagnetic interference. Widely applicable for dielectric loss measurement of transformers, mutual inductors, bushings, capacitors, lightning arresters and other equipment in the power industry.

Product Name: Dielectric Loss Tester, Anti Interference Dielectric Loss Tester, Fully Automatic Dielectric Loss Tester, Off Frequency Dielectric Loss Tester, Anti Interference Dielectric Loss Tester, Fully Automatic Dielectric Loss Tester

Product features

1. The instrument adopts the complex current method to measure capacitance, dielectric loss, and other parameters. The test results have high accuracy, making it easy to achieve automated measurement.

2. The instrument adopts frequency conversion technology to eliminate on-site 50Hz power frequency interference, and reliable data can be measured even in strong electromagnetic interference environments.

3. The instrument adopts a large screen LCD display, and the testing process is both intuitive and easy to operate through Chinese character menu prompts.

4. The instrument is easy to operate, and the measurement process is controlled by a microprocessor. As long as the appropriate measurement method is selected, the data measurement can be automatically completed under the control of the microprocessor.

5. Integrated model, equipped with standard capacitors and high-voltage power supply, convenient for on-site testing and reduces on-site wiring.

6. The instrument has high measurement accuracy and can meet the requirements of oil dielectric loss measurement. Therefore, only a standard oil cup and a dedicated testing line are needed to achieve oil dielectric loss measurement.

7. The CVT testing function can achieve self-excited testing of CVT without the need for external accessories. Only one measurement is required to measure the capacitance and dielectric loss of C1 and C2.

8. The reverse wiring test adopts IVDDV technology, eliminating the previous phenomenon of unstable reverse wiring data.

9. Equipped with reverse wiring low-voltage shielding function, C11 can perform 10kV reverse wiring dielectric loss measurement without disconnecting the wire when the 220kV CVT bus is grounded.

10. It has the function of measuring high voltage dielectric loss and can use high-voltage transformers or series resonance to conduct dielectric loss tests exceeding 10kV voltage.

11. Grounding protection function: When the instrument is not grounded or poorly grounded, it will not enter the normal program and will not output high voltage. The overcurrent protection function ensures that the instrument is not damaged in the event of a short circuit or breakdown of the test sample.

12. Electric shock protection function: When the instrument operator accidentally gets an electric shock, the instrument will immediately cut off the high voltage to ensure the safety of the test personnel.

Product parameters

Abnormal frequency dielectric loss testertechnical parameters

accuracy

Cx

± (reading x 1%+1pF)

tgδ

± (reading x 1%+0.00040)

Anti-interference index

Frequency conversion anti-interference, can still achieve the above accuracy under 200% interference

capacitance range

Apply high pressure internally

3pF~60000pF/10kV 60pF~1μF/0.5kV

Apply high pressure externally

3pF~1.5μF/10kV60pF~30μF/0.5kV

resolution

0.001pF, 4 significant digits

Range of TG δ

Unrestricted, with a resolution of 0.001%, automatic identification of three types of samples: capacitance, inductance, and resistance

Test current range

10μA to 1A

Apply high pressure internally

Set voltage range

0.5~10kV

output current

200mA

Boosting and lowering method

Continuous smooth adjustment

Test frequency: 45, 50, 55, 60, 65Hz single frequency; 45/55Hz, 55/65Hz, 47.5/52.5Hz automatic dual frequency conversion

Frequency accuracy

±0.01Hz

Apply high pressure externally

Test current 1A when connected in a positive direction, 40-70Hz at power frequency or variable frequency

When reversing the wiring, the test current is 10kV/1A, and the power frequency or frequency conversion is 40-70Hz

CVT self-excited low-voltage output method

Output voltage 3-50V, output current 3-30A

measure time

About 40 seconds, depending on the measurement method

input power

180V~270VAC, 50Hz ± 1%, powered by mains or generator

computer interface

Standard RS232 interface

printer

Thermal micro printer

ambient temperature

-10℃~50℃

relative humidity

<90%

Overall dimensions

460×360×350mm3

Instrument weight

28kg



Note: 1. The appearance of the product is subject to the actual product. Technical parameters and models are subject to change without prior notice. If there is any act of theft or copying, legal responsibility will be pursued.

2. For more information on ultra-high voltage products, please enter the product center.

异频介质损耗测试仪异频介质损耗测试仪异频介质损耗测试仪异频介质损耗测试仪异频介质损耗测试仪异频介质损耗测试仪异频介质损耗测试仪