Product Overview
AC/DC dual-purpose ultra lightweight test transformer(Test Transformer) is an intelligent withstand voltage testing equipment designed according to national power industry standards, with high performance. It is used to conduct insulation strength tests on various electrical products, electrical components, insulation materials, etc. under specified voltages to assess the insulation level of the product, discover insulation defects of the tested product, and measure the ability to withstand overvoltage. Widely used in electrical manufacturing departments, power operation departments, research institutions, and higher education institutions.
Technical parameters:
Specification, Model, Capacity (kVA), High Voltage (kV), High Voltage Current (mA), Low Voltage Input, Transformation Ratio (High/Meter), Temperature Rise (30 minutes)
Voltage (V) Current (A)
YDJ-3/50 3 50 60 200 15 500 10
YDJ-5/50 5 50 100 200 25 500 10
YDJ-10/50 10 50 200 200 50 500 10
YDJ-20/50 20 50 400 400 50 500 10
YDJ-30/50 30 50 600 400 75 500 10
YDJ-50/50 50 50 1000 400 125 500 10
YDJ-5/100 5 100 50 200 25 1000 10
YDJ-10/100 10 100 100 400 25 1000 10
Wiring method:
AC/DC dual-purpose ultra lightweight test transformerThe short-circuit rod of the high-voltage silicon stack should be extracted from the bushing to put the test transformer in a DC output state. Before conducting a DC leakage test, it is advisable to select the resistance value of the current limiting resistor (water resistor) based on the fact that the output terminal breaking current in the leakage test does not exceed the high-voltage silicon stack rectifier. Then, according to the requirements of the tested object for the DC high-voltage waveform, select the capacitance value of the high-voltage filtering capacitor. In order to improve the measurement accuracy of the applied voltage to the test sample, an FRC resistive capacitive voltage divider should be connected to the high voltage side to measure the voltage.
Environmental requirements:
1. Input voltage: AC 220V or 380V, 50Hz;
2. Environmental temperature: -40 ℃ to 40 ℃;
3. Relative humidity: ≤ 85% (when the ambient temperature is 25 ℃);
4. In an environment without chemical gases and vapors;
5. In non explosive gases;
6. In situations where rainwater does not infiltrate.