E-mail
977889474@qq.com
- Phone
-
Address
No. 159-9 Jinhu West Road, Jinhu Economic Development Zone, Jiangsu Province
Jiangsu Suyi Group Co., Ltd
977889474@qq.com
No. 159-9 Jinhu West Road, Jinhu Economic Development Zone, Jiangsu Province
0-100LEL Industrial and Commercial Point Type Combustible Gas Detector
1Introduction and Characteristics
0-100LEL Industrial and Commercial Point Type Combustible Gas DetectorIt adopts the currentDesigned and manufactured by combining imported sensors and highly stable chips. This instrument can still continuously detect flammable and toxic gases in unmanned hazardous environments, and can be widely used in places such as petroleum, chemical, power, smelting, pharmaceuticals, oil fields, oil depots, storage, environmental protection, fire protection, municipal and other places where there may be dangerous flammable or toxic gases. It is a monitoring instrument for personal safety and equipment safety. This deviceProduction inspection processaccording toJJG693-2011The national standard for combustible gas measurement and verification shall be implemented.
1AdoptingImported sensors with high sensitivity, low temperature drift, long lifespan, and minimal maintenance.
2、Reliable circuit design, highly stable use of chips and surface mount technology, good consistency and high reliability.
3Multiple signal outputs to choose from
4The4-20mAAnalog signal, switch signal, and485 Digital signals are available for multiple system choices(customizable).
5Easy to install, debug and maintain, instrument installation and wiring, debugging and maintenance are very convenient.
2、 Specification parameters:
| quantity Cheng | 0-100%LEL | Explosion-proof marking | Exd II CT6 |
| indication error | ≤±3%F.S | Operating Temperature | -40-70℃ |
| Small reading | 1%LEL | Operating Humidity | ≤90%RH |
| response time | ≤20second | size | 217*143*89mm |
| Sensor lifespan | 24month | weight | 1800g |
| Detection Principle | Catalytic combustion orNDIRinfrared | connecting cable | Three core shielded wire ≥RVVP3*1.0mm2 |
| Detection method | continuous work | Installation method | fixed bracket tube packaging wall-mounted |
| Working Voltage | 24V DC | output signal | 4-20mAthree-wire system+2Group switch quantity 485Bus system+2Group switch quantity |
| Explosion proof electrical interface | M20*1.5 | Fault Alarm | The automatic detection instrument displays corresponding fault codes in case of malfunction,Simultaneously outputting differential current signals or digital signals |
| material | die-cast aluminum |
3、 Application of gas detector:
This instrument can still continuously detect the concentration of flammable gases in unmanned hazardous environments and reach the alarm value for alarm. It can be widely used in places such as petroleum, chemical, power, smelting, pharmaceuticals, oil fields, oil depots, storage, environmental protection, fire protection, municipal and other places where there may be dangerous flammable or toxic harmful gases. It is a monitoring instrument for personal safety and equipment safety.