It is recommended to read this article first when selecting a magnetic flap level gauge!
Date: 2025-08-29Read: 12
Magnetic flap level gaugeComposed of the main body, flip box (composed of red and white dual color magnetic flip plates), float, flange cover, etc. In addition, components such as liquid level alarm, control switch, and liquid level transmitter can be equipped as needed to achieve functions such as upper and lower limit alarm, control, and remote display of liquid level.

Magnetic flap level gaugeWhen choosing, attention should be paid to:

1Clarify measurement requirements

Measurement range: The range is determined based on the liquid level height of the storage tank or container, and the range of a single unit generally does not exceed4500mmThe ultra long range requires segmented production and the addition of supporting flanges.

Medium characteristics:

Viscosity: The viscosity of the medium should be ≤0.4Pa·sTo avoid affecting the movement of the float.

Density: The medium density needs to be within0.52.0g/cmBetween 3, if the density is too low, a special float design is required. If the density is too high, the float may get stuck.

Corrosive: weakly corrosive medium is optional304or316Lstainless steel; Strong acid, strong alkali, and pressure ≤1.6MPaTemperature ≤120At ℃, PTFE lined anti-corrosion type should be selected.

2Determine the installation method

Side mounted: Suitable for most ordinary liquid storage tanks, installed on the side of the tank and connected to the medium inside the tank through a connecting pipe.

Top mounted: suitable for underground storage tanks, fire water tanks, etc., for liquid level measurement and installation maintenance from the top.

Inverted type: suitable for special scenarios such as underground liquid storage tanks, measuring liquid level from bottom to top.

3Select key parameters

Flange parameters:

Size: Measurement range ≤3000mmWhen, it is recommended to connect the flange size asDN50Measurement range>3000mmAt that time, it is recommended toDN80.

Pressure rating: It must comply with the relevant regulations of piping and equipment to ensure that the flange contact surface can correspond.

Accuracy requirement: Choose the appropriate accuracy according to the requirements, with a general measurement accuracy of ±10mm~±20mm.

Protection level: Select the protection level according to the on-site environment to ensure that the equipment works normally in harsh environments.