Performance characteristics:
Panel style structure, compact in appearance.
Front panel size: 110mm * 62mm
Shell size: 132mm * 91.5mm * 45mm
Hole size: 92.5mm * 45.5mm
Can be installed on the console or control cabinet; Can connect 6 350 ohm analog typessensor,
The excitation voltage is 10V; two rows of LED digital tubes display, making it easier to read;
A standard RS232/RS485 serial interface that can be used for standalone or networked data communication, printing and outputting;
18-36VDC DC input, low power consumption 8W;
The analog interface board provides two output modes: 0~10VDC/4-20mA.
Remote control of instrument calibration, zeroing, peeling, and various other functions through PLC, upper computer, and other methods;
CalFree calibration free technology;
The minimum calibration loading weight can reach 20% of the full range, which reduces the difficulty and workload of debugging while ensuring accuracy;
Working environment: -10~40 ℃, 10%~95% relative humidity, no condensation;
Storage environment: -40~60 ℃, 10%~95% relative humidity, no condensation;
Protection level: The front panel of IND320L meets the requirements of Type 4/12 (IP65).
The analog output expansion IND320L can be achieved through the optional analog interface board,
It can achieve analog output of 0~10V/4~20mA. Users can adjust the analog output.
Users do not need to load weights when adjusting analog output, as long as the IND320L has three levels of coarse adjustment, fine adjustment, and fine adjustment,
Coarse tuning can quickly adjust analog quantities to near the user specified rated output,
Fine tuning can make the output correspond to the rated output value.
Before adjusting the analog output, please calibrate the weighing system first; The analog accuracy of IND320L is 16 bits,
It is recommended that the A/D conversion accuracy of the load be no less than 14 bits.
To ensure safety, please make sure to use the power plug provided with the instrument during installation, and pay attention to the positive and negative poles.
Reversing the positive and negative poles of the power supply will not damage the instrument, but the instrument cannot be turned on normally.
The IND320L weighing instrument can only use DC power supply. If the 220V AC power supply is mistakenly connected, it will seriously damage the instrument.
BOM number: 72264026 Product model: 32L-1000-00-002-023 Basic type (common ground type) L00
BOM number: 72264027 Product model: 32L-1000-0A-002-023 Basic type (common ground type, analog output) L08