WP-8011-EX、WP-8012-EX、WP-8015-EX、WP-8121-EX、WP-8035-EX、WP-8036-EX、WP-8037-EX、WP-8038-EX、WP-8039-EX、WP-8041-EX、WP-8047-EX、WP-8067-EX、WP-8068-EX、WP-8069-EX、WP-8071-EX、WP-8072-EX、WP-8073-EX、WP-8074-EX
1、 Instrument Overview:
The WP-8000-EX series thermocouple isolation safety barrier receives thermocouple signals or other millivolt signals from hazardous areas on site, and after isolation and linearization processing, converts them into linearized DC signals for output to the control system or other unit combination instruments in the safe area.
Intelligent thermocouple isolation safety barrier. The thermocouple type and range can be configured and set.
This isolation safety barrier requires independent power supply, with electromagnetic isolation between the power supply input circuit output circuit.
2、 Features:
The thermocouple temperature transmitter isolates the output.
Intelligent, capable of on-site configuration settings, and can also select fixed thermocouple types and temperature range inputs.
Modular core design, no need for zero and full adjustment, automatic dynamic calibration of zero and automatic compensation for temperature drift.
Equipped with a working power indicator light.
Intrinsic safety input circuit Exia) IIC, input circuit overcurrent protection.
● Plug and unplug terminal block, DIN rail card installation.
3、 Main technical parameters:
working power supply
Power wiring; Independent wiring terminals 13-, 14+, can be plugged and unplugged with electricity
Power supply voltage; (20~30)VDC
Current loss:<30mA at 24VDC (one in one out)
< 45mA (one in and two out)
Power indicator; The power on LED light is on; green
Input signal (Exia) IIC danger zone
Input thermocouple types: K, E, S, B, R, T, N, W, J, and other types of thermocouples.
Optional input millivolt signal: (-5~60) mA; Or millivolt voltage range
Output circuit (safe zone)
Output current (4~20) mA
Allowable load for current output: 0~550 (4Ma~20Ma, 0~20mA output)
Output voltage: (1~5) V
Voltage output impedance: ≤ 500 Ω
Ripple (Vp-p): < 10mV
4、 Selection Table:
model |
input signal |
output signal |
number of channels |
WP-8072-EX |
ETheKTheSTheBTheRTheTTheJoptional
|
(4~20)mA/(1~5)VDC |
one in, one out |
WP-8074-EX |
ETheKTheSTheBTheRTheTTheJoptional
|
(4~20)mA/(1~5)VDC |
one in, two out |
Thermocouple type and range table:
Thermocouple type |
Temperature range(℃)
|
Zui small range(℃)
|
|
hot
electricity
by chance
|
K |
0~1300 |
120 |
E |
0~1000 |
80 |
S |
0~1600 |
580 |
B |
400~1800 |
1000 |
R |
-1200 |
850 |
T |
0~2300 |
120 |
N |
0~1200 |
180 |
W |
0~2300 |
340 |
J |
0~1200 |
100 |