E-mail
shzyyb18@163.com
- Phone
-
Address
Guanshengyuan Road, Xuhui District, Shanghai
Shanghai Ziyu Instrument Co., Ltd
shzyyb18@163.com
Guanshengyuan Road, Xuhui District, Shanghai
|
power supply |
|
|
Rated working voltage range |
DC24V±10% |
|
power consumption |
1.0W(24Power supply, single channel20mAOutput) 1.6W(24Power supply, dual channel20mAOutput) |
|
Dangerous side |
|
|
Input Signal Type |
Three-wirePT100.CU100.CU50.BA1.BA2(Confirm or configure the programmer for self programming when ordering) |
|
Safety side |
|
|
Output signal type |
Direct current:4-20mA(Required)0-10mA.0-20mA.1-5V.0-5V.0-10v.Please confirm the type of resistance and other signal when placing an order, or you can program it yourself |
|
Output load characteristics |
4-20mA:0-300Ω;0-10mA:0-600Ω;0(1)-5V:≥500KΩ;0-10V:≥1MΩ |
|
Switching Output |
Relay driving capability:125VAC/0.6A,30VAC/2A |
|
Relay response time: <5ms |
|
|
Transistor collector output: high levelVCC(≤30V)Low level ≤2.5V |
|
|
Transistor emitter output: high levelVCC-2.5VLow level ≤0.5V |
|
|
measurement accuracy |
0.2%FS±1character |
|
Dielectric Strength |
|
|
Local security end and non local security end |
2500V,a.c; 1min |
|
Cold Junction Compensation |
|
|
Compensation characteristics |
every20℃ error ±1℃ (compensation range:-25~+75℃) |
|
environmental condition |
|
|
ambient temperature |
0~50℃ |
|
ambient humidity |
5%~95%RH(Non condensing) |
|
standard |
|
|
electromagnetic compatibility |
conform toGB/T18268Application requirements for industrial equipment |
|
type name |
speak bright |
pour explain |
||
|
ZY-EXA |
Thermal resistance isolation safety barrier |
Range (℃) |
|
|
|
transport enter |
|
Default is single channel |
|
|
|
D |
Dual input channels (width)22.5mm) |
|
||
|
1 |
PT100 |
0~600 |
||
|
2 |
CU100 |
-50~150 |
||
|
3 |
CU50 |
-50~150 |
||
|
4 |
BA2 |
-199.9~600 |
||
|
5 |
BA1 |
-199.9~600 |
||
|
6 |
0-400Ω |
-1999~9999 |
||
|
output |
X |
No output (limited to)IIRoad) |
||
|
0 |
4-20mA |
analog output |
||
|
1 |
1-5V |
|||
|
2 |
0-10mA |
|||
|
3 |
0-5V |
|||
|
4 |
0-20mA |
|||
|
5 |
0-10V(Non switchable) |
|||
|
D1 |
RS485Output (limited to)IRoad) |
485output |
||
|
K1 |
Relay circuit contact |
Switching Output |
||
|
K2 |
transistor |
|||
|
Note: Analog output485Output and switch output cannot be selected simultaneously, and485Output is limited to output I. Please indicate the input range after selection when placing an order. Model example:BDE-EXA-C21 Thermal resistance isolation safety barrierThe two input signals arePT100The two output signals are4-20mA,PT100The input range is0~600℃. |
||||