The underground integrated fire pump room must meet the following conditions: the anti floating buried box pump integrated fire pump station should be located on the side or below the suction pool, and should not be adjacent to rooms that require quietness (such as broadcasting rooms, precision instrument rooms, research rooms, offices, classrooms, wards, bedrooms, etc.). Generally, it is recommended to set it on the ground floor. If it is set on the underground floor, there should be a safe passage leading to the outside and reliable noise reduction measures.

Product Details


The anti floating buried box pump integrated fire pump station should be located on the side or below the suction pool, and should not be adjacent to rooms that require quietness (such as broadcasting rooms, precision instrument rooms, research rooms, offices, classrooms, wards, bedrooms, etc.). Generally, it is recommended to set it on the ground floor. If it is set on the underground floor, there should be a safe passage leading to the outside and reliable noise reduction measures.

The independent water pump room in the community should be located near major water users, and the pump room, distribution room, and auxiliary rooms (such as maintenance rooms, duty rooms, bathrooms, etc.) should be built in one building; When adjacent to equipment rooms such as water heating rooms, refrigeration rooms, boiler rooms, and thermal centers, the shaft support room can be shared.


The underground integrated fire pump room must meet the following conditions

The anti floating buried box pump integrated fire booster water supply equipment (pump station) should have sufficient light and good ventilation. The heating temperature is generally not lower than 16 ℃, and for rooms without dedicated personnel on duty, the temperature should not be lower than 5 ℃ without freezing. The basement or semi underground pump room should have effective ventilation facilities to discharge hot air, and the air exchange rate in the pump room should not be less than 4 times per hour.

The integrated fire-fighting booster water supply equipment (pump station) with anti floating buried box pump should be equipped with at least one gate or installation port that can enter and exit the equipment (or components). 3) The pump room should be equipped with drainage ditches (generally not less than 200mm wide) and collection pits, and the ground should have a slope of 0.01 towards the drainage ditch (the longitudinal slope of the drainage ditch should not be less than 0.01). When the collection pit cannot self discharge, submersible sewage pumps can be used to lift and discharge. The number of water pumps should not be less than two. At the same time, an electrical automatic control device should be installed in the water accumulation pit to start the pump at high water level, stop the pump at low water level, and start both pumps at the same time as the alarm water level


The height of the integrated fire-fighting booster water supply pump station with anti floating buried box pump shall be determined according to the following regulations:

Fire protection tasks and pump rooms that do not allow intermittent water supply should have two independent external power sources. The layout of the anti floating buried box pump integrated fire booster water supply equipment (pump station) in the pump room includes the layout of the pump room units, the layout of the suction and discharge pipes, etc. The layout of anti floating buried box pump integrated fire booster water supply equipment (pump station) pump room units in residential pump rooms is relatively small, and generally adopts a single row layout. The layout should comply with the requirements of Table 10.2-13. When using a combination unit, the distance between the unit and the surrounding area should not be less than 1.2m.