DDFB485typeTemperature and humidity transmitterforRS-485Bus type, usingRS485interface,Can achieve simultaneous monitoring of multiple points,Networking and remote transmission, with on-site digital display function.
1.contact method
This product adoptsRS485/RS232(Customizable) interface method, using widely used in the industrial fieldModbusThe data communication protocol enables direct connection with various control devices, display instruments, and computers for data communication.
2.Remote transmission function
adoptRS485interface,The maximum transmission distance is1200rice.It can achieve remote monitoring and control of temperature and humidity.
3.Networking function
Multiple DDFB485 unitsThe transmitters are connected in series through a bus, and each transmitter requires an external power supply for separate power supply. The bus endpoint is connected to the computer serial port through a digital signal converter. Multi point monitoring centered around the receiving device can be achieved to achieve centralized control and management over a large area. The same network can monitor up to32A monitoring point.
4.On site display
DDFB485?The model also has on-site display function, which can directly observe the temperature and humidity changes on site through the display panel.
parameter |
technical indicators |
measurement range |
0%RH-100%RH 0℃~60℃ |
measurement accuracy20%RH—80% RH@25℃ |
humidity: ±5.0%RHtemperature: ±0.5℃ |
Interface method |
RS485/RS232 |
communication distance |
less than1200m |
communication protocol |
standardModbus |
response time |
1.6s |
Editable address |
1-255 |
Baud rate |
DB485DGMType is2400~38400 |
power supply voltage |
7-40V |
Integrated transmitter operating temperature |
-10℃—60℃ |
power consumption |
less than4W |
When using this product for the first time, initialization settings must be made to complete the parameter settings for communication between the device and the upper computer. The adjustable parameters include: baud rate setting (1200bps, 2400bps, 9600bps, 19200bps, 38400), communication address setting (001->255). The specific setting method is as follows:
DDFB485?The parameters of the model can be set through the peripheral keyboard, and the specific method is as follows:
DDFB485?Dial Settings
M :Function key, confirmation key
C :Exit button
▲: Up key
▼: Down button
Parameter settings for the panel:
Address setting
Long press the M key, the LCD will display the settings menu, * page
Set the address within the range of 1 to 255
Adjust the address code using the ▲ and ▼ keys, and once the adjustment is complete
Press the M key again to confirm the settings, and press the C key to exit the settings
state
Baud rate setting
Long press the M key, the LCD will display the settings menu, press M again
Switch to the second page baud rate setting interface with the key, baud rate setting
The range is 2400-38400, which can be accessed through the ▲ and ▼ keys
Adjust the baud rate and press the M key for the third time after the adjustment is complete,
Confirm the settings and press the C key to exit the settings state.
display switching
Pressing the ▲ or ▼ keys during normal display can switch between displaying humidity and dew point data. When entering the functional realm
If there is no operation or pressing the C key for 10 seconds after the face or setting interface, the setting will exit
The data will not be saved.


4、 Installation and use
The main body of this product is wall mounted installation, which can be fixed on walls, cabinet side walls, and other places.

Figure 1. Dimensions of the transmitter
After the installation of the transmitter host is completed, power supply and communication can begin:


Figure 2. DB485GM Wiring Instructions
The transmitter follows the standardRS485For the communication interface, the communication protocol adopts the widely used one in the industrial fieldModbusCommunication protocol, multiple transmitters backup through485Bus serial connection, each device is powered separately by an external power supply, and the bus endpoint is connected to the computer serial port through a digital signal converter. For specific networking and terminal connection methods, please refer to the diagram3, picture4.

Figure 3. Schematic diagram of lead connection

picture4.Networking diagram