- Phone
-
Address
200 Qingyu Road, Jiading District, Shanghai
Shanghai Blueprint Machinery Equipment Co., Ltd
200 Qingyu Road, Jiading District, Shanghai
Spot German Yifumen IFM Capacitive Sensor AL1102Product Details
Spot German Yifumen IFM Capacitive Sensor AL1102
Reliable transmission of machine data, process parameters, and diagnostic data to the controller
Connect up to eight IO Link devices
Integrate PROFINET interface
Durable casing suitable for harsh industrial environments
application
applicationI/O modules for on-site applications
Chrysanthemum Chain FunctionFieldbus interface
Electrical data
Working voltage [V]20... 30 DC; (US; according to SELV/PELV)
Current loss [mA]300...3900; (US)
protection levelIII
Sensor power supply US
Maximum current load total [A]3.6
Overall input/output
Total number of inputs and outputs16. (configurable)
Total number of inputs and outputsNumber input: 16; Number of digital outputs: 8
input
Number of input digits16; (IO-Link Port Class A: 8 x 2)
High switch level [V]11...30
Low switch level [V]0...5
Digital input protection short circuithave
output
Number of digital outputs8; (IO-Link Port Class A: 8 x 1)
Maximum current load per output [mA]300
short circuit protectionhave
interface
communication interfaceEthernet; IO-Link
Ethernet - PROFINET
Transmission standards10Base-T; 100Base-TX
transmission rate10; 100
agreementPROFINET
Factory settings
IP address: 0.0.0.0
Subnet Mask: 0.0.0.0
gateway IP addresse: 0.0.0.0
MAC address: Refer to the model label
Interface Description
Supported network topologies: wired
ring
IO-Link Master
Transfer type
IO-Link revision1.1
Port quantity level A8
working conditions
Environmental temperature [° C]-25...60
Storage temperature [° C]-25...85
Maximum allowable relative air humidity [%]90
Shell protection levelIP 65; IP 66; IP 67
Protection level (NEMA 250)6P
Pollution level2
chemical medium
ISO 16750-5
AA, BA, BD, HLP, CC, DB, DC, DD, CA
NEMA 250 5.13.1
AA
Certification/Testing
EMC electromagnetic compatibility
EN 61000-6-2
EN 61000-6-4
impact-resistant
DIN EN 60068-2-27
earthquake resistance
DIN EN 60068-2-64 2009-04
DIN EN 60068-2-6 2008-10
MTTF [year]78
Mechanical technical data
Weight [g]396
raw materialsShell: PA orange; Socket: Nickel plated brass
sealing materialFKM
annotation
annotation
For other information, please refer to the user manual
packaging unit1 piece
Electrical Connection - Ethernet
IN / OUT X21, X22Connector: M12; Decoding: D; Sealing ring: FKM
Electrical Connection - Power Supply
X31Connector: M12; Decoding: A
Electrical Connection - System Interface
IO-Link Port Class A X01...X08Connector: M12; Decoding: A; Sealing ring: FKM