- Phone
-
Address
508, Building A, Incubator No.1, Innovation Valley, Changqing District, Jinan City
Shandong Snow Electronics Co., Ltd
508, Building A, Incubator No.1, Innovation Valley, Changqing District, Jinan City
Independent combustible gas detectors suitable for small catering establishmentsProduct Features:
high measurement accuracy
The sensor adopts imported gas sensitive components with high accuracy and good linearity.
Reliable and stable performance
Adopting excellent software digital processing system with good anti-interference performance.
It has automatic diagnosis and protection functions for over concentration, short circuit, and open circuit.
Explosion proof type
Explosion proof design, suitable for use in hazardous areas of Zone 1 and Zone 2 under factory conditions.
Multiple signal outputs
RS-485/4-20mA/contact signal. M-BUS dual bus has no polarity signal output.
Applicable Environment
Suitable for various harsh environments.
Easy installation and maintenance
Design a dedicated installation bracket for quick on-site installation. Modular design, direct plug and replace.
Independent combustible gas detectors suitable for small catering establishmentsMain technical indicators:
1. Detection principle: catalytic combustion type
2. Detecting gases: methane, propane, isobutane
3. Measurement range: 3-100% LEL
4. Service life: 3 years
5. Alarm points: Low segment alarm value of 20% LEL, high segment alarm value of 50% LEL
6. Indication error: ≤± 5% F · S
7. Response time: ≤ 30 seconds
8. Detection method: diffusion type
9. Working mode: Long term continuous work
10. Explosion proof type: Explosion proof type
11. Explosion proof mark: ExdIICT6Gb/ExtDA21IP66T80 ℃
12. Protection level: IP66
13. Power supply: DC24V
14. Rated power: 2W
15. Signal transmission distance: ≥ 1000 meters
16. Usage environment: Temperature -40 ℃~+70 ℃ Humidity ≤ 95% RH
17. Atmospheric pressure: 86kPa~106kPa
18. Dimensions: 163 × 176 × 80mm
Independent combustible gas detectors suitable for small catering establishmentsWorking Principle:
The detector is mainly composed of sensors, microcontrollers, operational amplification circuits, communication chips, etc. The sensor converts the gas concentration into an analog electrical signal, which is then amplified through operation, converted into a digital signal by a microcontroller, and finally converted into a digital signal through a communication chipM-BUS/4-20mA/RS485 standard signal, uploaded to the controller.