- Phone
-
Address
Room 1501-1502, Caoyang Business Building, 889 Zhongjiang Road, Putuo District, Shanghai
Shanghai Weitelui Industrial Development Co., Ltd
Room 1501-1502, Caoyang Business Building, 889 Zhongjiang Road, Putuo District, Shanghai
ASCO has numerous brands under its umbrella, among which ASCO/READHAT and SIRAI brands include universal products and some products suitable for special industries, which can control ordinary media. GENERALCONTROL is a combustion series valve, and the medium can be fuel, etc. SCIENTIFIC is a microvalve suitable for the medical device and other analytical product industries. JOUCOMATIC is a professional brand of pneumatic control products, while TRI-POINT is a pressure temperature switch product.
Selection criteria for ASCO solenoid valves in the United States
1. Select the solenoid valve based on pipeline parameters: diameter specification (i.e. DN), interface method
1) Determine the diameter (DN) size according to the on-site pipeline inner diameter size or flow requirements;
2) Interface method, generally>DN50 requires flange interface, ≤ DN50 can be freely selected according to user needs.
2. Select the material and temperature group of the solenoid valve based on fluid parameters
1) Corrosive fluids: corrosion-resistant solenoid valves and all stainless steel should be selected; Edible ultra clean fluid: It is recommended to use food grade stainless steel solenoid valves;
2) High temperature fluid: It is necessary to choose electromagnetic valves made of high-temperature resistant electrical materials and sealing materials, and to choose piston type structures;
3) Fluid state: up to gaseous, liquid, or mixed state, especially when the diameter is greater than DN25, it must be distinguished;
4) Fluid viscosity: Usually below 50cSt, it can be freely selected. If it exceeds this value, a high viscosity solenoid valve should be used.
3. Selecting solenoid valves based on pressure parameters: principles and structural types
1) Nominal pressure: This parameter has the same meaning as other general valves and is determined based on the nominal pressure of the pipeline;
2) Work pressure: If the work pressure is low, the principle of direct action or step-by-step direct action must be selected; When the low working pressure difference is above 0.04Mpa, direct acting, step-by-step direct acting, and pilot operated can all be selected.
4. Electrical selection: The voltage specifications should preferably be AC220V or DC24, which are more convenient.
5. Choose based on the duration of continuous work: normally closed, normally open, or continuously powered on
1) When the solenoid valve needs to be opened for a long time and the duration exceeds the closing time, the normally open type should be selected;
2) If the opening time is short or the opening and closing time is not long, choose the normally closed type;
3) However, for some working conditions used for safety protection, such as furnace and kiln flame monitoring, the normally open type cannot be selected, and the long-term electrified type should be selected. Divided into direct acting, pilot operated, and manual reset valves.
6. Select auxiliary functions according to environmental requirements: explosion-proof, check, manual, waterproof fog, water shower, and diving.
ASCO solenoid valve is a type of solenoid valve with a sealed chamber and through holes at different positions. Each hole is connected to a different oil pipe. The middle of the chamber is a piston, and there are two electromagnets on both sides. The valve body will be attracted to which side when the magnet coil on the other side is energized. By controlling the movement of the valve body, different oil discharge holes can be opened or closed. The oil inlet hole is normally open, and hydraulic oil will enter different oil discharge pipes. Then, the pressure of the oil will push the piston of the cylinder, which in turn drives the piston rod, which drives the mechanical device. In this way, the mechanical motion is controlled by controlling the current on and off of the electromagnet
The above content is provided by Shanghai Weite Rui; For details, please click:Selection criteria for ASCO solenoid valves in the United States