E-mail
1368553620@qq.com
-
Phone
13625506311
-
Address
Tianchang City, Chuzhou City, Anhui Province
Anhui Donglin Automation Instrument Complete Set Co., Ltd
1368553620@qq.com
13625506311
Tianchang City, Chuzhou City, Anhui Province
SWP7061 signal conversion isolator/Changhui/Changhui digital display instrument/Changhui Automation System/Changhui Temperature Display/Changhui Digital Display/Changhui Inspection Instrument/Changhui Automotive Electrical Co., Ltd/Changhui transmitter/Changhui Instrument Manual/Changhui Electric/Changhui digital display SWP7000 series signal isolator is an electrical equipment connected between industrial field instruments and control rooms. It effectively solves the on-site interference problem of industrial automation control systems by reliable isolation between power supply, input, and output, ensuring the stable and reliable operation of the system. It is a universal product that basically covers various signal isolation, conversion and other functional requirements in the system.SWP7061 signal conversion isolator
Changhui Signal Distributor
Model |
additional code |
Explanation |
||
SWP7061 |
/□ |
|
one in, one out |
Signal input: 0~1KΩ,4~20mA,0~20mA 1~5V,0~5V,0~10V,0~100mV |
SWP7062 |
/□ |
/□ |
one in, two out |
|
SWP7063 |
/□ |
/□ |
two in, two out |
|
Channel 1 output type |
/I |
|
Signal output: 4~20mA,0~20mA 1~5V,0~5V,0~10V |
|
/V |
|
|||
Channel 2 output type |
/I |
|||
/V | ||||
Note: When placing an order, the input and output types must be specifically specified.
Specifications |
Explanation |
power supply |
20~35VDC |
Power consumption |
24V power supply, 20mA output: ≤1.5W(SWP7061) ≤2.8W(SWP7062) ≤3.0W(SWP7063) |
On site signal |
Output current: 4-20mA, 0-20mA Load resistance: ≤ 450 Ω Output voltage: 1-5V, 0-5V, 0-10V Output impedance:<10 Ω Output load: ≥ 10K Ω |
Control room signal |
Input current: 4-20mA, 0-20mA Input voltage: 1-5V, 0-5V, 0-10V Input resistance: 0-1K Ω |
power protection |
Reverse power protection |
output accuracy |
0.2%F.S |
temperature drift |
0.01%F.S/℃ |
Instrument structure |
Nylon plastic shell structure |
Applicable on-site equipment |
Two line valve positioner, electrical converter, etc |