SWP-T805 Light Column PID Self tuning Controller

NegotiableUpdate on 06/08
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

Does the SWP-T805 light column PID self-tuning controller provide customized processing? Product model: SWP-PID Measurement accuracy: 0.1% FS External dimensions: 9648110mm (mm) Hole size: 9244mm SWP-LED series PID self-tuning controller/PID light column display control instrument is suitable for systems that require high-precision measurement control. It can automatically calculate the optimal PID control parameters based on the controlled object. SWP-LED series PID self-tuning controller/PID light column display control instrument set

Product Details

1、 Main featuresSWP-T805 Light Column PID Self tuning Controller

1. PID parameter self-tuning.

2. It can be equipped with one PID control output and one transmission output, suitable for various measurement and control scenarios.

3. Manual/automatic undisturbed switching, parameters can be modified in manual mode.

4. It has multiple adjustable output modes (PWM output, controllable trigger output, solid-state relay output, and voltage/current output).

2、 Special technical parametersSWP-T805 Light Column PID Self tuning Controller

Control output mode

PWM output, thyristor triggered output, solid-state relay output, voltage/current output

Setting/Display Accuracy

+0.5% FS+1 digit max. The set value matches the displayed value without any relative error

Scale range

0.0% -100.0% (unit: 0.1%)

Integral (reset) time

0-9999s (unit: 1s)

Differential (ratio) time

0-9999s (unit: 1s)

control cycle

1-250s (unit: 1s)

sampling period

0.5s

3、 Instrument appearance and wiring diagram (the following is the basic wiring method, please refer to the random wiring diagram for special orders)

4、 SWP-LED series PID parameter self-tuning control instrument type chart

Model

code

explain

SWP -N

□□□□□ - □□□□□ - □□ - □

New generation PID self-tuning controller

Appearance characteristics

D
S

Horizontal display instrument

Vertical display instrument

External dimensions

1

4

7

8

9

48×48mm

96 × 48mm (horizontal) 48 × 96mm (vertical)

72×72mm

160×80mm 80×160mm

96×96mm

Control function

05

PID self-tuning control

Communication method

0

2

4

8

9

No communication

The communication interface is RS-232C

The communication interface is RS-422

The communication interface is RS-485

Special specifications for communication interfaces

control output

Refer to 'Control Output Mode'

Transmission output

Refer to 'Transmission Output Method'

Input type

□□

Refer to 'Input Types'

*Alarm method

N

H

L

No alarm (can be omitted)

Upper limit alarm

Lower limit alarm

Second alarm method

N

H

L

No alarm (can be omitted)

Upper limit alarm

Lower limit alarm

Feed output

P

DC24V power supply output

Power supply mode

W

T

DC24V power supply

AC90-265V power supply (switch mode power supply)

AC220V power supply (linear power supply, can be omitted)

5、 SWP-LED series PID light column display control instrument type chart

model

code

Remarks

SWP -N

T □□□ - □□□□ - □□ - □□ - □ - □

New generation light column PID display controller

External dimensions

8

160 × 80mm (horizontal), 80 × 160mm (vertical)

Control function

05

PID self-tuning control

Communication method

0

2

4

8

9

No communication

The communication interface is RS-232C

The communication interface is RS-422

The communication interface is RS-485

Special specifications for communication interfaces

control output

Refer to 'Control Output Mode'

Transmission output

Refer to 'Transmission Output Method'

Input Type

□□

Refer to 'Input Types'

*Alarm method

N

H

L

No alarm (can be omitted)

Upper limit alarm

Lower limit alarm

Second alarm method

Refer to 'Alarm Methods'

Feed output

P

Feed output

Power supply mode

W

T

DC24V power supply

AC90-265V power supply (switch mode power supply)

AC220V power supply (linear power supply, can be omitted)

Appearance features

X

Horizontal display

Vertical display (can be omitted)

★ Input type:

code

Input type

Measurement range

code

Input Type

Measurement range

code

Input type

Measurement range

01

B

400~1800℃

09

Pt100.1

-99.9~199.9℃

17

30~350Ω

-1999~99999 d

02

S

0 ~1600 ℃

10

Cu50

-50.0~150.0℃

18

Special specifications

User specific

03

K

0 ~1300 ℃

11

Cu100

-50.0~150.0℃

19

4-20 mA square root

-1999~99999 d

04

E

0 ~1000 ℃

12

4~20 mA

-1999~99999 d

20

0-10mA square root

-1999~99999 d

05

T

-200~400℃

13

0~10 mA

-1999~99999 d

21

1-5 V square root

-1999~99999 d

06

J

0 ~1200 ℃

14

1~5 V

-1999~99999 d

22

0-5V square root

-1999~99999 d

07

Wre

0 ~2300 ℃

15

0~5 V

-1999~99999 d

23

Switchable input

Please refer to the table below for details

08

Pt100

-200~650℃

16

0~20 mA

-1999~99999 d

★ Full switching input only requires setting the secondary parameters of the instrument to switch input multiple division marks. The division marks that can be input are as follows:

code

Input Type

code

Input Type

code

Input Type

code

Input type

code

Input Type

01

B

05

T

09

Pt100.1

14

1~5 V

21

1-5 V square root

02

S

06

J

10

Cu50

15

0~5 V

22

0-5V square root

03

K

07

WRe

12

4~20 mA

19

4-20 mA square root

04

E

08

Pt100

13

0~10 mA

20

0-10mA square root

★ Transmission output mode

Selection code

0

2

3

4

5

8

Output

no-output

4~20mA

0~10mA

1~5V

0~5V

Special specifications

★ Alarm output mode

Selection code

N

H

L

G

A

D

Output method

No alarm (can be omitted)

Upper limit alarm

Lower limit alarm

Deviation internal alarm

Deviation outside alarm

LBA alarm

★ Control output mode

Selection code

0

1

2

3

4

5

6 7 8

Output

no-output

relay

4~20mA

0~10mA

1~5V

0~5V

SCR output SSR output Special specifications

★ Note: There is only one D105 alarm output.

The control output is PID control, and the transmission output is the transmission output corresponding to the measured value. The D405 and S405 series can only choose PID control output.

★ For the same division number, the selection code and instrument programming code are different. Please pay attention when setting the instrument.

★ Model example:

SWP-D805-21-08-HL-P-W

PID self-tuning controller, communication mode RS232, output mode relay output, input type Pt100, * alarm is upper limit alarm, second alarm is lower limit alarm, power supply output, DC24V power supply, horizontal meter.


The above is a detailed introduction to SWP-PID self-tuning controller/PID light column display controller, including the price, model, pictures, manufacturer and other information of SWP-PID self-tuning controller/PID light column display controller!