- Phone
-
Address
509, Building 4, Lane 680, Shuishe West Road, Baoshan District, Shanghai
Shanghai Wangxu Electric Co., Ltd
509, Building 4, Lane 680, Shuishe West Road, Baoshan District, Shanghai
WXZG-B2 Portable DC System Grounding Fault Finder
Product Overview:
The portable DC system grounding fault locator is a product successfully developed by our company by introducing new phase advance processing and data transfer algorithm technologies from abroad. This instrument enables rapid detection of various grounding and mixed line faults in DC systems, solving the problems caused by various grounding methods such as virtual grounding, high resistance grounding, multi-point grounding, single point grounding, low resistance grounding, direct grounding, mixed line grounding, loop grounding, capacitor grounding, AC grounding, transistor isolation grounding, etc. with poor insulation status. It can quickly locate and locate faults. The instrument can also accurately detect the grounding resistance value, grounding direction, fast fault location, and has functions such as voice intelligence, graphic expression, and direction indication. It is a high-precision detection instrument for DC system grounding fault inspection and positioning.
WXZG-B2 Portable DC System Grounding Fault Finder
Features:
1. This instrument is divided into a fault analyzer and a fault locator. The analyzer is powered directly from the bus, without the need for external AC or battery power, making operation more convenient;
2. Solved all faults such as virtual grounding with poor insulation status, high resistance grounding, multi-point grounding, single point grounding, low resistance grounding, direct grounding, mixed line grounding, loop grounding, capacitor grounding, AC grounding, transistor isolation grounding, etc;
3. Eliminate grounding faults in the DC system, avoid interference from large capacitors distributed on site, accurately lock the fault in a small range and locate it;
4. Accurately indicate the direction of grounding signal current, provide voice explanation, and quickly locate the grounding fault point;
5. Accurately detect the magnitude and phase of the leakage current in the circuit, and quickly and accurately locate the fault point based on the magnitude and phase changes of the leakage current before and after the grounding fault point;
6. DC systems below 500V share a set of DC grounding detectors and do not have any other special requirements for DC voltage;
7. Signal output power: < 0.15W, internal current limiting protection, no impact on relay protection, automation devices, and operation circuits, safe to use;
8. Ripple analysis and digital oscilloscope function: using spectrum analysis function to solve various interference signals, view waveform information of various detection signals and circuits;
9. Intelligent current clamp, automatically detects the open and closed status of the current clamp, compatible with both large and small jaws;
10. Capable of adapting to grounding caused by AC/DC surge, ring network power supply grounding, diode isolation power supply grounding, and high resistance grounding;
11. No need for installation, no need for power outage, no need to disconnect or shake insulation, quickly locate grounding faults;
12. Luxurious outer packaging, easy to carry.
Technical Specifications:
A. Analyzer:
Working voltage: directly powered from the busbar (24V~260V)
Detection range of busbar grounding resistance: 0-999 K Ω
Measurement accuracy of busbar grounding resistance: error ≤ 5%
Bus voltage measurement range: 0-600V
Measurement accuracy of bus voltage: 1%
Communication intrusion measurement range: 0-300V
Communication penetration measurement accuracy: 1%
Power consumption: less than 10W
Dimensions (length x width x height): 238 x 134 x 45 (mm)
Weight: 1.7 kg
Suitable temperature: -10 ℃ -+50 ℃
B. Positioning device:
Working voltage: 12V (for lithium battery operation, the working voltage is 10.8V~12.6V)
Branch grounding resistance detection range: 0-1000 K Ω
Measurement accuracy of branch grounding resistance: error ≤ 5%
Measurement current value of branch grounding resistance: 0.005mA
Power consumption: less than 1W
Dimensions (length x width x height): 238 x 134 x 45 (mm)
Weight: 1.5 kg
Suitable temperature: -10 ℃ -+50 ℃
C. Signal source parameters:
Signal source high current ≤ 1mA
Signal source high power ≤ 0.01W
Signal source peak PPm ≤ 5V
Signal source high frequency ≤ 2.5Hz
Signal source high stability ≤ 1%
Working power supply: lithium battery power supply (rechargeable)