- Phone
-
Address
509, Building 4, Lane 680, Shuishe West Road, Baoshan District, Shanghai
Shanghai Wangxu Electric Co., Ltd
509, Building 4, Lane 680, Shuishe West Road, Baoshan District, Shanghai
Product Overview
The DC short-circuit device ampere second characteristic testing system is a commonly used protective component in DC systems of power system substations and power plants. Its good performance and practicality have been unanimously recognized and widely applied. At present, the DC power supply network mostly adopts a tree structure, from the battery to various electrical equipment in the station, generally passing through at least three levels of distribution. With the increasing demand for DC power supply in power plants and substations to control loads and power loads, the requirements for overload protection and short circuit protection of their protective electrical appliances are also becoming more and more strict. They cannot have any refusal or misoperation, especially over level misoperation, which will cause damage to power equipment and system failures, and even lead to large-scale power outages. The occurrence of over class misoperation is mainly due to unreasonable selection of protective electrical appliances and unstable performance of circuit breakers. Due to the inappropriate short-circuit characteristics of DC circuit breakers, during the operation of DC systems, when short-circuit faults occur in the underlying electrical equipment, it often causes the tripping of the higher-level DC circuit breaker, which is also known as leapfrog tripping. This leads to power outages in other feeder lines, further expanding the fault and seriously endangering the safe operation of the power grid. In order to prevent such over class tripping accidents, it is necessary to test the ampere second characteristics of various small DC circuit breakers in the DC system, determine the tripping time of circuit breakers under different short-circuit currents, effectively analyze the ampere second characteristics and protection level coordination of small DC circuit breakers, and verify whether the level difference coordination between upper and lower circuit breakers in the DC system is reasonable.
However, the technical specifications of small DC circuit breakers currently used in the power system are provided by manufacturers at the time of equipment delivery. On site maintenance personnel are unable to confirm whether the safety characteristics of small DC circuit breakers meet the requirements due to the lack of corresponding testing methods. Moreover, operational practice has proven that over time, the safety characteristics of the equipment will also change, especially after 3 years of operation, if the technical indicators of the equipment deviate, the typical consequence is a change in the characteristics of the circuit breaker, resulting in refusal or misoperation.
At present, the institutions and manufacturers in China that conduct small-scale DC circuit breaker ampere second characteristic testing use fixed equipment for DC circuit breaker ampere second characteristic testing, such as fixed high current power supplies and large load resistors, which are large in size and weight, and are not convenient for mobile testing. Analytical instruments are conventional instruments such as voltmeters, ammeters, oscilloscopes, etc., with complex wiring and inconvenient use, and are not suitable for mobile testing needs in various substations. To solve the problem of detecting the actual characteristics of small DC circuit breakers on site, we have independently developed a set of DC circuit breaker ampere second characteristic testing system suitable for mobile use in power systems.
This instrument is launched based on long-term on-site operation experience and multiple advanced technologies at home and abroad. It can achieve the detection and testing of the ampere second characteristics of small DC air switches with different capacities, providing a constant high current of 1-1000A, and can output larger currents through expansion. can
Test the tripping time of the circuit breaker under different short-circuit currents to verify whether the ampere second characteristics of the circuit breaker meet the requirements. This instrument adopts a new high-speed microprocessor and is equipped with a large screen LCD display. On site operation has shown that the instrument has excellent functionality, high reliability, simple structure, and easy operation.
GDAS-1000 DC Circuit Breaker Ampere Second Characteristics Testing System
Features
characteristic
function
According to the GB10963-1999 standard for overcurrent protection circuit breakers used in household and similar places, circuit breakers should undergo a trip characteristic test.
Starting from the cold state, apply a current of 1.13In (agreed non trip current) to the circuit breaker until the agreed time, and the circuit breaker should not trip. Then, within 5 seconds, stabilize the current to a current of 1.45 In (specified tripping current), and the circuit breaker should trip within the specified time.
Starting from the cold state, a current of 2.55In should be applied to each stage of the circuit breaker, and the disconnection time should be greater than 1s. For circuit breakers with a rated current of 63A or less, the disconnection time should be less than 60s, and for circuit breakers with a rated current greater than 63A, the disconnection time should be less than 120s.
For B-type circuit breakers: starting from the cold state, apply a current of 3In to each stage of the circuit breaker, and the disconnection time should be greater than 0.1s; then starting from the cold state, apply a current of 5In to each stage of the circuit breaker, and the disconnection time should be less than 0.1s.
For C-type circuit breakers: starting from the cold state, apply a current of 5In to each stage of the circuit breaker, and the disconnection time should be greater than 0.1s; then starting from the cold state, apply a current of 10In to each stage of the circuit breaker, and the disconnection time should be less than 0.1s.
For D-type circuit breakers: starting from the cold state, apply a current of 10In to each stage of the circuit breaker, and the disconnection time should be greater than 0.1s; then starting from the cold state, apply a current of 50In to each stage of the circuit breaker, and the disconnection time should be less than 0.1s. Both tests should meet the time current action characteristic table.
| experiment | type | Test current | initial state | Limit when tripped or not tripped | expected result |
| a | B 、 C , D | 1.13In | cold state | t≧1h(In≦63A) t≧2h(In>63A) | Do not release |
| b | B 、 C 、 D | 1.45In | Immediately following Experiment A | t<1h(In≦63A) t<2h(In>63A | trip |
| c | B 、 C 、 D | 2.55In | cold state | t<1h(In≦63A) t<2h(In>63A) | Do not release |
| d | B 、 C 、 D | 3In,5In 10In | cold state | 1s 1s | trip |
| e | B 、 C 、 D | 5In 10In50In | cold state | t<0.1s |
|
|
|
Main technical parameters