PEC-ZDT acquisition terminal detection device

NegotiableUpdate on 03/31
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin
Overview
PEC-ZDT acquisition terminal detection device
Product Details

This device mainly tests the functions and data transmission protocols of specialized transformer acquisition terminals, distribution transformer monitoring terminals, and centralized meter reading terminals (concentrators, collectors).

Main testing items

Inspection Item

Specialized variable acquisition terminal

transformer terminal unit

Concentrator collector

data collection

Pulse collection experiment

l

Analog quantity acquisition test

l

l

State quantity collection test

l

l

Electric energy meter data acquisition test

l

l

l

Data Management and Storage

Real time and current data

l

l

l

Historical daily data testing

l

l

l

Historical monthly data testing

l

l

l

Key user collection

l

Parameter Setting and Query

Clock calling and timing

l

l

l

Terminal parameters

l

l

l

Meter reading parameters

l

l

l

Other: Prepaid and other parameters

l

l

l

Control experiment

Time control function

l

Factory rest control function

l

Business report suspension control function

l

Current power down float control

l

Monthly electric energy constant value control

l

Purchase of electrical energy(Fei)control

l

Reminder alarm function

l

Power protection function

l

Rejection function

l

Remote control testing

l

l

Event log

Power purchase parameter setting event

l

Password error event

l

l

l

Active electric energy differential exceeds the limit

l

voltage/Current over limit event

l

l

l

Power supply impact test

Power phase failure test

l

l

l

Power supply voltage variation test

l

l

l

power consumption

l

l

l

Data and clock retention test

l

l

l

Ground fault resistance test

l

l

l

Harmonic influence test

l

l

l

Frequency influence test

l

l

l

Inspection Item

Specialized variable acquisition terminal

transformer terminal unit

Concentrator collector

Event log

Time period changes in electricity meter rates

l

l

Change of programming time for electric energy meter

l

l

Change of meter reading date for electric energy meter

l

l

Constant change of electric energy meter

l

l

Reset the maximum demand of the electric energy meter to zero

l

l

Change in phase failure frequency of electric energy meter

l

l

Changes in the number of times the electric energy meter loses voltage

l

l

Changes in the number of power outages on the energy meter

l

l

Battery undervoltage of electric energy meter

l

l

Event of decrease in electrical energy expression

l

l

Electric energy over tolerance event

l

l

Electric energy meter flying away event

l

l

Electric energy meter shutdown event

l

l

The time of the electric energy meter exceeds the tolerance

l

l

Terminal meter reading failure event

l

l

Terminal parameter change event

l

l

l

Reverse current event

l

l

Voltage phase failure event

l

l

Loss of pressure event

l

l

Terminal phase sequence abnormal event

l

l

Terminal stopped/Power on event

l

l

l

voltage/current unbalance

l

l

data transmission

Cascade function

l

l

Data forwarding function

l

l

l

Relay (routing) function

l

Scheduled task reporting

Scheduled sending1class data

l

l

Scheduled sending2class data

l

l

Reliability of data collection

Accuracy of data collection

l

l

Success rate of data collection

l

other

Terminal initialization function

l

l

l

72Continuous power on for hours

l

l

l

Terminal prefabricated parameter inspection

l

l

l

Security protection function

l

l

l



2.jpg

1Accuracy level of the device:0.05Grade.

2Range: Voltage Range:30380VCurrent range:0. 1A25A(Automatic gear setting, automatic range switching)

3Output capacity: Voltage output: determined by the number of meter bits; Current output: determined by the number of digits on the meter

4Phase sequence: The output three-phase voltage and current are in positive phase sequence, or can be set in reverse phase sequence; Output power fully controlled digital regulation

5Voltage regulation: regulation range: set range0120%Adjust fineness:10%1%0.1%0.01%

6Current regulation: regulation range:0.005A25AAdjust fineness:10%1%0.1%0.01%

7Phase adjustment: Adjustment range:0°~360°; Adjust fineness:10°1°0.1°0.01°

8Frequency adjustment: Adjustment range:45.0065.00HzAdjust fineness:5Hz1Hz0.1Hz0.01Hz

9Output power stability:0.1%

10Distortion degree of output voltage and current waveform:0.5%The distortion of the current waveform shall not exceed1%

11The harmonic of the device can be set simultaneously for voltage and current, as well as for phase separation. Any phase output can contain multiple harmonic components.

12The monitoring values of voltage, current, power, power factor, phase, frequency, etc. of this device are all taken from the indications of the multifunctional standard meter, standard table

The level shall not be lower than the level of the device, Therefore, there is no need to separately verify the monitoring table. The set value of the output power can be compared with the measured value of the standard meter

The difference between them is considered as the error of the monitoring instrument.

13Test standard pulse output: frequency0.0520HzProgram control adjustment, adjust fineness0.01HzThe amplitude is5V12VThe number of pulses every1a

Program controlled adjustment of pulse width and fineness1ms

14DC analog output: Current output:2.520mA (Automatic gear setting, automatic range switching), adjust fineness0.01%

Accuracy of current output: per level5110%The citation error is better than0.2%, output stability:0.02%/1min

15Time calibrator indicator: frequency measurement accuracy ±0.2PPMDaily error accuracy: ≤10ms

Frequency measurement range:0.01Hz10kHzInternal crystal oscillator stability: ≤5×10-8/s

16Terminal AC auxiliary power supply: single-phase:100V220VError ±10%Frequency:50Hz±2%Total output capacity:500600VA

17The device has a voltage drop test function

18Maximum power consumption of the device: determined by the size of the load, with a maximum not exceeding3000VA

19Device voltage resistance:> AC 2000V/10mA/1minInsulation resistance:> 10MΩ

20Working environment: The working environment should be dust-free, free of corrosive gases, shock resistant, and have sufficient sunlight.

Ambient temperature20±2℃; Relative humidity ≤85%R.HGrid voltage220V±10%Grid frequency:50 Hz±1%