Functional Features |
Provide LCD and digital display, local data query;
High precision real-time measurement of electrical parameters such as three-phase voltage, current, power, power factor, frequency, zero sequence voltage, zero sequence current, voltage current imbalance, voltage phase angle, and average voltage and current;
Time of use electricity metering and timed meter reading of time of use electricity;
Measure the 2-31st harmonic distortion rate of three-phase voltage and current (optional);
2-31st harmonic components, voltage and current K factor;
Measure the maximum demand data for active and reactive power in both forward and reverse directions;
Multiple rate time-sharing measurement of positive and negative active energy, combined reactive energy, and four quadrant energy (optional);
Provide multi loop control nodes, which can be used for alarm, trip and other control (optional);
Support multi-channel 4-20mA analog transmission output (optional);
Supports RS-485 communication, Modbus RTU protocol, Modbus TCP protocol, 645-2007 communication protocol;
Support multiple switch input (DI) and multiple relay output (DO) (optional);
Pulse output (active pulse, reactive pulse, second pulse software optional);
Electricity level supports querying data for the current month, previous month, and previous month;
Support 32 SOE displacement records;
Support 32 event records (event enablement can be set to: overcurrent, overvoltage, undervoltage, phase loss, imbalance, zero sequence overcurrent, zero sequence overvoltage, etc.);
Support the function of querying the maximum demand and the occurrence time of the maximum demand for the current, last month, and the previous month.
Support power on and power-off recording function.
Programmable setting of current voltage ratio;
Easy installation, simple wiring, and small engineering quantity;
Multiple appearance options to meet the requirements of different cabinet electrical circuits
|
Technical indicators |
| measurement accuracy | Active energy: 0.5S level, 1 level, 0.2S level |
| Reactive power: Level 1, Level 2 | |
| input parameter | Wiring methods: single-phase, three-phase three wire, three-phase four wire |
Rated voltage: AC 57.7V, AC100V, AC220VAC380V (can be customized according to requirements) | |
| Rated current: AC1A, AC5A | |
|
Overload: Voltage: 1.2 times (continuous), 2 times/1 second (instantaneous) Current: 1.2 times (continuous), 10 times/5 seconds (instantaneous) | |
| Frequency: 45~65Hz (conventional 50Hz, 60Hz) | |
| Working power supply | Scope of work: AC/DC 80V~270V |
| Power consumption:<5VA | |
| secure | Insulation resistance:>100M Ω |
| AC withstand voltage: AC 2kV | |
| environment | Normal operating temperature: -25 ℃ to+55 ℃ |
| Extreme working temperature: -40 ℃ to+70 ℃ | |
| Storage and transportation temperature: -40 ℃ to+70 ℃ | |
| Storage and working humidity: ≤ 85%, non corrosive gas environment | |
| Atmospheric pressure: 80Kpa to 110Kpa | |
| Altitude: ≤ 5000m | |
| functional module | Communication interface: RS-485 communication, Modbus RTU protocol,Modbus TCP protocol, 645-2007 communication protocol,Baud rate 1200~19200bps, default 2400bps |
Switch input: supports multiple dry node inputsPassive contact input, built-in power optocoupler isolation | |
Switching output: supports multiple relay outputs,Capacity: AC 250V/5A, DC 30V/5A | |
Transmission output: Supports multiple analog outputs: 4-20 mA (default)0~20mA、0~5V、0~10V | |
| mechanical parameters | Frame dimensions (mm): 72 × 72, 80 × 80, 96 × 96, 120 × 120; |
| Hole size (mm): 67 × 67, 76 × 76, 91 × 91, 110 × 110; |

| Product Outline Dimensional Drawing |

|
Product standards |
GB/T 17215.321 "Special Requirements for AC Measuring Equipment Part 21 Static Active Energy Meters (Class 1 and Class 2)"
GB/T 17215.322 "Special Requirements for AC Measuring Equipment Part 22 Static Active Energy Meters (0.2S and 0.5S Levels)"
GB/T 17215.323 "Special Requirements for AC Measuring Equipment Part 23: Static Reactive Energy Meters of Class 2 and Class 3"
GB/T 22264.1 "Installed digital display electrical measuring instruments - Part 1: Definitions and general requirements"
GB/T 22264.2 "Installed digital display electrical measuring instruments - Part 2: Special requirements for ammeters and voltmeters"
GB/T 22264.3 "Installed digital display electrical measuring instruments - Part 3: Special requirements for power meters and reactive power meters"
GB/T 22264.7 "Installed digital display electrical measuring instruments - Part 7: Special requirements for multifunctional instruments"
GB/T 22264.8 "Installed digital display electrical measuring instruments - Part 8: Recommended test methods"