The HYWJF-30kW non partial discharge withstand voltage test device meets the 220kVPT induction withstand voltage partial discharge test. Equipped with a large screen display, it can indicate: output voltage, output current, ambient temperature, outlet air temperature, output voltage waveform of variable frequency power supply, date and time, countdown time, and fault information display; Waiting for the function of setting experimental parameters.
HYWJF-30kWNo partial discharge voltage withstand test device——Basic configuration:
1. Main components of the equipment:
serial number |
Device Name |
Model and Specifications |
unit |
quantity |
prepare note |
1 |
No partial discharge frequency conversion
power supply
|
HYWJF-30kW |
Taiwan |
1 |
30kW,30~300Hz,≤10pC,
Output: Single phase0~350V
|
2 |
partitionleavechangeCompressor |
WJQ-30kVA/350V/400V |
Taiwan |
1 |
capacity30kVAOutput:400VLow voltage:350V,≤10pC |
2. Equipment accessories:
serial number |
name call, name, say, weigh |
Model and Specifications |
unit |
quantity |
Remarks |
1 |
Power input cable |
10mm2 |
root |
2 |
5m/root |
2 |
Variable frequency power output cable |
10mm2 |
root |
2 |
5m/root |
3 |
Connect wiring |
|
set |
1 |
|
HYWJF-30kWNo partial discharge voltage withstand test device——Protection function:
(1)Input voltage protection:When the input power supply is under voltage, unbalanced, or out of phase, the corresponding protection circuit in the control box will activate, cutting off the high voltage output and prompting an alarm on the screen.
(2)Overvoltage protection:It can be set arbitrarily. When the output voltage value of the complete set of equipment reaches the protection setting value, the output will be automatically cut off and an alarm will be prompted on the screen.
(3)Short circuit (overcurrent) protection:When the output of the frequency conversion cabinet is short circuited or the output current reaches the protection setting value, the output can be automatically cut off and an alarm will be prompted on the screen.
(4)Breakdown flashover protection:When discharge or ground flashover occurs on the high voltage side, the output can be automatically cut off.
(5)Zero protection:The voltage must be boosted from zero, otherwise the output will not start.
(6)Power failure protection:When the input power suddenly loses power, the system uses the remaining power in the circuit to promptly shut down the output signal, ensuring the safe shutdown of the system.
(7)Overtemperature protection:The air temperature at the entrance and exit is displayed on the screen in real-time, and the data is processed by the microcontroller according to the different ambient temperatures. If the variable frequency cabinet exceeds the temperature limit, an alarm message will be issued.
(8)Cooling fan linkage protection:When the fan fails to operate due to a malfunction, the variable frequency power supply cannot start orAutomatic cut-offOutput. At the same time, it has the function of automatically identifying the phase sequence of the fan power supply, without the need for phase replacement.
(9)loseVoltage limit function protection:When setting the high voltage, during the experiment, ensure that the output voltage does not exceed the set high voltage in case of misoperation or abnormal situations.
(10)Phase loss protection:When the input power is out of phase and cannot function properly, the screen will display 'out of phase' and the system will be shut down.
(11)Overload protection:When the output current exceeds the set current, the control box automatically shuts off the output of the variable frequency power supply, and there is a corresponding prompt at this time.
HYWJF-30kWNo partial discharge voltage withstand test device——Technical Specifications:
No partial discharge variable frequency power supplyHYWJF--30kW-1 unit |
partitionleavechangeCompressorWJQ-30kVA/ 350V/400V-1 unit |
Input power supply:three-phase380V±10%,50Hz |
Rated capacity of low-voltage winding:30kVA |
Rated output power:30kW |
Rated voltage of low-voltage winding:350V |
Rated output voltage: single-phase0~350V, Continuously adjustable |
Input current:85.7A |
Rated output current:85.7A |
Rated capacity of high-voltage winding:30kVA |
Output waveform: Standard sine wave |
high voltage winding: 400V |
Waveform distortion rate:≤1.0% |
tallpresselectricityflow:75A |
Output voltage instability: ≤1.0% |
Partial discharge under rated voltage≤10pC |
Output frequency:30~300Hz |
|
Cooling method: forced air cooling |
|
Frequency adjustment resolution:0.1Hz |
|
Output frequency instability: ≤0.1% |
|
Insulation level: Input and output terminals to ground≥2kV/AC/1min |
|
Allowable operating time: Continuous operation is allowed at rated capacity |
|
Noise level:≤65dB |
|
Partial discharge capacity: at rated voltage and rated current≤10pC |
|