MS7918 Thermal Resistance Input Signal Isolator (Intelligent Type)
1、 Characteristics
1 in 2 out
·Suitable for thermal resistance inputs such as Pt100 and Cu50
·Programmable input type and range settings
·Isolated output 4-20mA or 1-5V
2、 Technical specifications
|
·Accept thermal resistance signal input, and output standard DC signal to the control system or other instruments through isolated transmission. is an intelligent thermal resistance input temperature transmitter that can be programmed with a PC and control software to set the input type and range. And it can verify the zero point and full degree of the output signal. One input, two outputs. DC power supply mode, with magnetic and electrical isolation between the input and output of the power supply, as well as between each channel. Standard 35mm DIN rail card installation. Plug and unplug wiring terminal with spring compression connection. It can be used in conjunction with unit combination instruments, DCS, PLC and other systems, and is widely used in various temperature detection and control systems in industrial production processes. ● Input (Can be set through PC and software programming) Thermistor: P1100, Cu50, etc Temperature range: Depending on the type of sensor connected (see range table) Connection form of thermal resistance sensor: 2-wire or 3-wire system Allow wire resistance: Each wire should be below 10 Ω ● Output Output signal: 4~20mA, 1~5V, or other specified signals Load resistance: ≤ 550 Ω when outputting 4-20mA (factory default) When outputting 1-5V, ≥ 100K Ω |
● Power supply Supply voltage range: 20-30VDC Rated supply voltage: 24VDC Current consumption (when powered by 24VDC):<50mA ● Comprehensive parameters Standard accuracy: ± 0.1% (refer to the table of thermal resistance types, ranges, and measurement errors) Temperature drift: Basic error/10 ℃ Response time:<10ms Isolation capability: 2.5KV, 1min.50Hz between input output power supply Insulation resistance: ≥ 100M Ω/500VDC between input output power supply Working environment temperature: -20-+60 ℃ Storage environment temperature: -40~+80 ℃ Shell material/protection level: PC (polycarbonate) material/IP20 Dimensions: 16 × 116 × 110 (mm) |
3、 Model selection

![]()
![]()
4、 Dimensions and installation diagram
● Installation
1.35mm standard DIN rail card installation. Please pay attention to the stability and firmness of the card position during installation.
2. Install vertically as much as possible to facilitate heat dissipation inside the instrument.
● Typical applications
1. Used to provide distribution voltage to on-site transmitters and isolate and convert input signals.
2. Devices connected to the site: Active electrical signals from two-wire or three wire non smart transmitters.
3. Connect to the control system (or other unit combination instruments): The AI card of each DCS/PLC receives current or voltage signals.

● External dimensions
Width (thickness) x height x depth=16 x 116 x 110 (mm)

5、 Terminal wiring diagram
Terminal wiring: Plug and unplug terminal blocks, connected by self boosting spring type compression. The cross-sectional area of the wire shall not exceed 2.5mm2Multiple bundles or single stranded cables.